Installation and Operation Manual

Solar Inverters MX Mark III series

© Autarco Group B.V.

Содержание MX Mark III Series

Страница 1: ...Installation and Operation Manual Solar Inverters MX Mark III series Autarco Group B V...

Страница 2: ...l is an integral part of the unit Please read the manual carefully before installation operation or maintenance Keep this manual for future reference Product information is subject to change without n...

Страница 3: ...iew 11 4 Installation 12 4 1 Safety 12 4 2 Mounting instructions 12 4 3 Safety clearance 13 4 4 Mounting procedure 14 5 Electrical installation 15 5 1 AC connection 15 5 2 DC connections 18 5 3 Invert...

Страница 4: ...11 1 General 29 11 2 Internal component fault 29 11 3 Grid errors 30 11 4 System and design fault 31 12 Product specifications 32 4 MX Mark III series Inverters...

Страница 5: ...fety instructions which if not correctly followed could result in burns 1 2 Target Audience This manual is intended for anyone who uses Autarco MX MIII series inverter Before any further action the op...

Страница 6: ...S2 MX5000 MIII S2 MX6000 MIII The S2 In the product code means the product is a grid tied inverter If the product has an S at the end it comes with integrated DC switches The item code or SKU will inc...

Страница 7: ...e with IEC 61730 class A WARNING The PV inverter will become hot during operation please don t touch the heat sink or peripheral surface during or shortly after operation NOTICE Do not directly connec...

Страница 8: ...DANGER HIGH ELECTRIC VOLTAGE This device is directly connector to public grid All work to the inverter shall be carried out by qualified personnel only There might be residual currents in inverter fo...

Страница 9: ...installation and operation manual CE MARK This equipment conforms to the basic requirements of the EU guideline governing low voltage and electromagnetic compatibility M S2 MX MIII EN V0 3 9...

Страница 10: ...iciency of 97 7 Wide MPPT voltage range Low turn off voltage High enclosure protection class IP66 Integrated power export limitation management Integrated DC arc fault protection Silent design using c...

Страница 11: ...installation and operation manual 3 3 Product overview M S2 MX MIII EN V0 3 11...

Страница 12: ...to intense sunshine is not recommended 4 2 Mounting instructions The inverter is suitable for outdoor and indoor installation Vertical installation is recommended with a maximum inclination of 15 back...

Страница 13: ...installation and operation manual 4 3 Safety clearance Caution Make sure heat sinks are out of reach of children Observe the following minimum clearances to walls M S2 MX MIII EN V0 3 13...

Страница 14: ...ting procedure Step 1 Mount the wall bracket onto the mounting wall with appropriate screws plugs Step 2 Lower the inverter onto the bracket and secure with the locking screws 14 MX Mark III series In...

Страница 15: ...tect the volume of the leakage current and compare it with the expected value if the leakage current exceeds the permitted range the RCPD will disconnect the inverter from the AC load If regulations i...

Страница 16: ...d adapter to the cable Step 2 Strip outer jacket 60mm and strip each cable insolation about 12 1mm Step 3 Insert cable strands into connector socket and lock the screws Make sure to fit the ground wir...

Страница 17: ...ways use separate fuses for consumer load Use dedicated circuit breakers with load switch functionality for load switching The selection of the mains circuit breaker rating depends on the wiring desig...

Страница 18: ...4mm or 6mm PV cable and MC4 connectors For details on how to assemble MC4 connector please refer our MC4 connector manual DANGER For protection against electric shock MC4 connectors must be isolated f...

Страница 19: ...e if not connected yet 2 Connect DC side if not connected yet 3 Switch ON the DC switch 4 Switch ON the AC switch 1 Switch OFF the AC switch 2 Switch OFF the DC switch NOTICE Please ensure the correct...

Страница 20: ...normally When inverter DC switch and AC switch have been turned on the inverter will start initializing After approx 3 minutes the inverter will start normal operation with the inverter display showi...

Страница 21: ...AC VALUE A Shows the voltage V of the grid Shows the current A of the grid Status VALUE Power VALUE W Shows the status of the inverter Shows current output power W of the inverter For any status other...

Страница 22: ...n can be scrolled through with UP DOWN keys to see the information as per the table below Press ENTER key to enter a submenu Press ESC key to go back to the main menu Alarm Messages Scroll through the...

Страница 23: ...tandards AS4777 VDE0126 EN50549 G83 User defined Press ENTER key to save the setting Press ESC key to cancel and return When selecting User defined the following upper and lower values have to be set...

Страница 24: ...y to revise the value Press ENTER key to save Press ESC key to return Special settings ONLY for maintenance person STD Model settings ONLY for using in Australia Restore Settings Press ENTER key to re...

Страница 25: ...installation and operation manual The output power of the inverter varies with ambient temperature as shown in the figure below M S2 MX MIII EN V0 3 25...

Страница 26: ...ow is the recommended connection diagram when using the Autarco supplied meter NOTICE Only RJ45 connection is allowed If supplied cable is not long enough we recommend the purchase of an RJ45 extender...

Страница 27: ...Select Meter in Grid and press ENTER Go to Internal EPM set Set Backflow Power Select the allowed export power and press ENTER Go to Internal EPM set Fail safe On Off Select your preference and press...

Страница 28: ...dissipate heat Any dirt or dust can be removed with a cloth or soft brunch CAUTION Do not touch the heat sink when the inverter is in operation Turn OFF the inverter see section 5 3 and allow for cool...

Страница 29: ...ler 11 2 Internal component fault Error type Display message Error code Error description Action Over BUS DC voltage OV BUS 1021 Internal fault 1 Restart inverter up to three times 2 If error persists...

Страница 30: ...in the inverter 1 Wait to see if the grid frequency returns within limits 2 If a problem persists check whether the grid standard is set correct in Advanced Settings see 6 6 3 Check grid frequency in...

Страница 31: ...detected in the system 1 Restart inverter up to three times 2 Call installer to a Check for pinched crimped or otherwise damaged cables and connections b Check all switches for short circuit 3 If err...

Страница 32: ...12 Product specifications 32 MX Mark III series Inverters...

Страница 33: ...installation and operation manual M S2 MX MIII EN V0 3 33...

Страница 34: ...34 MX Mark III series Inverters...

Страница 35: ...installation and operation manual M S2 MX MIII EN V0 3 35...

Страница 36: ...36 MX Mark III series Inverters...

Страница 37: ...installation and operation manual M S2 MX MIII EN V0 3 37...

Страница 38: ...38 MX Mark III series Inverters...