Hot Domestic Water (HDW) pump controller

AURATON 1107

Congratulations  on  your  purchase  of  the  AURATON  1107 

controller.  Our  device  will  save  you  energy  and  ensure 
thermal comfort for many years. 

Before  you  start  using  the  controller,  please  read  this 

instruction carefully.

1. APPLICATION

AURATON 1107

 is intended for automatically switching on 

and off circulation pumps depending on the temperature. 

In hot domestic water (HDW) systems, the controller-pump 
assembly forces circulation of water in HDW systems with 
coal-fired and gas-fired boilers without systems controlling 
the  operation  of  the  pump.  The  controller’s  sensor 
measures the water temperature in the HDW tank.

In  HDW  systems,  the  controller  maintains  constant 
temperature of water in the tank or in the HDW circuit.

The range of settings for the HDW pumps is from 20°C to 
80°C. The hysteresis (difference between the temperature 
at which the device is switched on and off) is equal to 4°C. 

2. INSTALLATION

2.1. Mounting the controller.

ź

support using two screws (the concrete anchors with 
screws are delivered with the controller).

ź

The cables extending from the controller must be fixed 
to the wall.

2.2. Mounting the sensor.

ź

Install the sensor in the HDW tank.

NOTE:  The  sensor  must  not  be  immersed  in  liquids 

or installed at flue gas outlets to the stack

.

The controller must be mounted on a wall or another 

EN

AURATON 

1107

User Manual

The 

GUARD

  system  installed  in  the 

AURATON  1107

 

controller prevents seizure of the rotor of unused pump. 

If  the  pump  is  not  used  for  a  long  time,  the  built-in 
processor  starts  the  pump  automatically  for  30  seconds 
every 14 days.  

NOTE: In order for the system to work after a long period 

of  non-use,  the  AURATON  1107  controller  must  be 
switched on at all times.

2.3. Connecting  the  power  supply  cable  to  the 

pump.

ź

Connect  the  yellow  or  yellow-green  conductor 

(ground  or  protective  neutral  grounding)  to  the 
(       ) terminal .

ź

Connect the blue wire to the ( 

N

 ) terminal.

ź

Connect the brown wire to the ( 

L

 ) terminal.

2.4. Checking the connection.

ź

Check if the wire is connected properly and fix the lid 
of the terminal box to the pump’s motor with screws.

2.5. Connecting the controller.

ź

After  the  wires  are  secured  to  prevent  accidental 
pulling, 

connect the power supply cable to a 230 V/50 

Hz power outlet with a grounding pin. The ambient 
temperature  in  the  place  where  the  controller 
is installed must not exceed 40°C

.