6.
Electrical connection
6.1.
Basic information
Electric shock due to presence of hazardous voltage!
Failure to observe this warning can result in death, serious injury, or property damage.
→
The electrical connection must be carried out exclusively by suitably qualified
personnel.
→
Prior to connection, observe basic information contained in this chapter.
Wiring diagram/terminal
plan
The pertaining wiring diagram/terminal plan (in German or English) is attached to
the device in a weather-proof bag, together with these operation instructions. It can
also be requested from AUMA (state order number, refer to name plate) or
downloaded directly from the Internet (http://www.auma.com).
Permissible networks
(supply networks)
The actuators are suitable for use in TN and TT networks with directly grounded star
point for nominal voltages up to maximum 690 V AC. Use in IT network is permissible
for nominal voltages up to maximum 600 V AC. For IT networks, a suitable, approved
insulation monitor measuring the pulse code is required.
Current type, mains
voltage, mains fre-
quency
Type of current, mains voltage and mains frequency must match the data on the
name plate.
Figure 19: Name plate example
[1]
Type of current
[2]
Mains voltage
[3]
Mains frequency
Risk of immediate actuator operation when connecting to mains!
Risk of personal injuries or damage of the valve.
→
After connection and prior to switching on mains power, set the selector switch
to OFF.
Figure 20: Selector switch set to OFF
The selector switch is not a mains switch. When positioned to OFF, actuator control
is prevented. The actuator power supply remains connected.
External supply of the
electronics
For external electronics supply, the power supply of integral controls must have an
enhanced isolation against mains voltage in compliance with IEC 61010-1 and the
output power be limited to 150 VA.
Protection and sizing on
site
For short-circuit protection and for disconnecting the actuator from the mains, fuses
and disconnect switches have to be provided by the customer.
23
TR-M30X – TR-M1000X
TR-MR30X – TR-MR1000X
Electrical connection