Features and functions of actuator
Coupling unbored
Standard:
Coupling
●
Coupling unbored extended
●
Finish machining of coupling (standard or extended)
-
Bore according to EN ISO 5211 with 1 keyway according to DIN 6885-1
-
Square bore according to EN ISO 5211
-
Two-flat according to EN ISO 5211
Options:
Dimensions according to EN ISO 5211
Valve attachment
Features and functions of actuator controls
Standard voltages:
1-phase AC current – Voltages/frequencies
230
115
Volt
50/60
50/60
Hz
Permissible variation of mains voltage: ±10 %
Permissible variation of mains frequency: ±5 %
For current consumption, current type, mains voltage and frequency, refer to the name plate
Mains voltage, mains frequency
24 V DC +20 %/–15 %
Current consumption: With options up to 200 mA
The external power supply must have a reinforced insulation against mains voltage in accordance with
IEC 61800-5-1 and may only be supplied by a circuit limited to 150 VA in accordance with IEC 61800-
5-1.
External supply of the electronics
(option)
Category III according to IEC 60364-4-443
Overvoltage category
Power electronics with integral motor controller
Power electronics
The controls are designed for the rated motor power, refer to separate Electrical data
Rated power
Operation commands and setpoint via Modbus RTU interface
Control
(input signals)
Via Modbus RTU interface
Status signals
(output signals)
●
Push buttons OPEN, STOP (LOCAL - REMOTE), CLOSE
●
2 multi-colour programmable indication lights:
-
End position CLOSED (yellow), fault/failure (red), end position OPEN (green),
operation mode LOCAL (blue)
Standard:
Local controls
Local controls mounted separately on wall bracket
Option:
●
Switch-off mode adjustable:
-
Limit or torque seating for end position OPEN and end position CLOSED
●
Torque monitoring across the whole travel
●
Torque by-pass
●
Programmable EMERGENCY behaviour:
-
via Modbus RTU interface
-
Reaction can be selected: Stop, run to end position CLOSED, run to end position OPEN
●
Positioner:
-
Position setpoint via Modbus RTU interface
-
Programmable behaviour on loss of signal
-
Automatic adaptation of the dead band (adaptive behaviour selectable)
-
Switch-over between OPEN - CLOSE control (REMOTE OPEN-CLOSE) and setpoint control
(REMOTE SETPOINT) via Modbus RTU interface
Functions
Plug/socket connector with crimp connection
Standard:
Electrical connection
Welded or sealed plug/socket connector (100 bar when connected)
Option:
Refer to name plate
Wiring diagram
Settings/programming the Modbus RTU interface
The Modbus address is set via switches (DIP switches in the actuator), alternatively also via parameters
(using AUMA Software CDT and AUMA service cable Z100.999). Parity and baud rate are set via
parameters.
Setting the Modbus RTU interface
43
SVM 05.1 – SVM 07.5 / SVMR 05.1 – SVMR 07.5
Modbus RTU
Technical data