Activate operation mode Remote by means of local controls:
→
If indication light [4] is blinking in blue: Hold down push button [2] for approx. 3
seconds until the blue indication light goes out.
➥
Now, the actuator can be remote-controlled via fieldbus.
Change-over between OPEN - CLOSE control and setpoint control:
For actuators equipped with a positioner, it is possible to select between OPEN
CLOSE control (Fieldbus REMOTE/Fieldbus CLOSE ) and setpoint control
(Fieldbus SETPOINT).
EMERGENCY operation:
●
An EMERGENCY operation is initiated by the Fieldbus EMERGENCY command
bit.
●
The actuator moves to a predefined EMERGENCY position (i.e. end position
OPEN or end position CLOSED).
●
During EMERGENCY operation, the actuator does not react to other operation
commands such as Fieldbus/OPEN/Fieldbus/CLOSE or Fieldbus SETPOINT.
24
SVM 05.1 – SVM 07.5 / SVMR 05.1 – SVMR 07.5
Operation
Modbus RTU