17. Accept value or cancel?
→
Accept value: Press .
→
Cancel process without accepting the value: Press
C
.
➥
Display indicates:
EDIT
M1210
OPENING
100%
:EDIT
C:ESC
EDIT
M1211
CLOSING
100%
:EDIT
C:ESC
Use and to select between
OPENING
and
CLOSING
.
18. Return to status display:
→
Press
C
several times until
S0
is displayed.
Information
The following fault signals are sent if the torque setting performed has been reached
in mid-travel:
●
Status indication
S0: Operation mode OFF/LOCAL = FAULT IND.
●
Status indication
S0/S6: Operation mode REMOTE = FAULT IND.
●
Status indication
S1: TORQUE FAULT (OPEN)
or
TORQUE FAULT
(CLOSE)
(torque fault)
The fault has to be acknowledged before the operation can be resumed. The
acknowledgement is made:
●
either by an operation command in the opposite direction.
-
For
TORQUE FAULT (CLOSE)
: Operation command in direction OPEN
-
For
TORQUE FAULT (OPEN)
: Operation command in direction CLOSE
●
or, in case the torque applied is lower than the preset tripping torque:
-
via the push button Reset in selector switch position LOCAL.
9.6
Limit switching: set
Via the menu to parameter:
MAIN MENU (M0)
SETTINGS (M1)
SET LIMIT SWITCHES (M10)
CLOSED POSITION (M100)
OPEN POSITION (M101)
Step by step:
1.
Set selector switch to position 0 (OFF).
45
SGExC 05.1 – SGExC 12.1 Control unit: electronic (MWG)
ACExC 01.1 Non-Intrusive
Commissioning (basic settings)