![AUMA SG 04.2 Скачать руководство пользователя страница 21](http://html1.mh-extra.com/html/auma/sg-04-2/sg-04-2_operation-instructions-manual_3016497021.webp)
7.2.
Switch compartment: open/close
Figure 18:
The following sub-assemblies are located within the switch compartment:
●
End position detection
●
RWG electronic position transmitter (option)
●
Mechanical position indicator
The switch compartment must be opened to perform the setting of these
sub-assemblies.
Open
1.
Loosen screws [2] and remove cover [1] from the switch compartment.
Close
2.
Clean sealing faces of housing and cover.
3.
Check whether O-ring [3] is in good condition, replace if damaged.
4.
Apply a thin film of non-acidic grease (e.g. petroleum jelly) to the O-ring and
insert it correctly.
5.
Place cover [1] on switch compartment.
6.
Fasten screws [2] evenly crosswise.
21