5.5.1.
Terminal compartment: open
Figure 29: Open terminal compartment
[1]
Cover
[2]
Screws for cover
[3]
O-ring
[4]
Blanking plugs
[5]
Cable gland (example)
[6]
Connection frame
Hazardous voltage!
Risk of electric shock.
→
Disconnect device from the mains before opening.
Flameproof enclosure, danger of explosion!
Risk of death or serious injury.
→
Before opening, ensure that there is no explosive gas and no voltage.
1.
Loosen screws [2] and remove cover [1].
2.
Insert cable glands suitable for connecting cables.
Information: When selecting cable glands observe type of protection (with Ex d
approval) and enclosure protection NEMA... (refer to name tag).
The type of protection stated on the name tag, NEMA... , is only ensured if
suitable cable glands are used.
Figure 30: Name tag, example with enclosure protection NEMA
Information: For shielded cables: Use EMC approved cable glands.
3.
Seal cable entries unused cable entries with approved plugs suitable for the
required protection type.
30
SAEx 25.1 – SAEx 35.1 / SAREx 25.1 – SAREx 30.1
Electrical connection
NORM (without controls)