9.
Enter password (
→
enter password).
➥
Display shows the set value.
➥
The bottom row indicates:
Edit Esc
10.
Press
Edit
.
Change value
11. Enter new value for tripping torque via
Up ▲ Down ▼
.
Information: The adjustable torque range is shown in round brackets.
12. Save new value via
Save
.
➥
The tripping torque is set.
13. Back to step 4 (CLOSED or OPEN): Press
Esc
.
Information
The following fault signals are issued if the torque setting performed has been reached
in mid-travel:
●
In the display of the local controls: Status indication
S0007 Fault
=
Torque fault OPEN
or
Torque fault CLOSE
The fault has to be acknowledged before the operation can be resumed. The
acknowledgement is made:
1.
either by an operation command in the opposite direction.
-
For
Torque fault OPEN
: Operation command in direction CLOSE
-
For
Torque fault CLOSE
: Operation command in direction OPEN
2.
or, in case the torque applied is lower than the preset tripping torque:
-
in selector switch position Local control (LOCAL) via push button RESET.
-
in selector switch position Remote control (REMOTE):
-
via the fieldbus, command reset., if the fieldbus is the active command
source.
-
via a digital input (I/O interface) with RESET command if a digital input
is configured for signal
RESET
and the I/O interface is the active
command source.
10.3.
Fieldbus address (slave address), baud rate, parity and monitoring time: set
Customer settings M0041
Modbus M0341
MD1 slave address M0247
MD2 slave address M0409
Baud rate M0343
Parity/stop bit M0782
Monitoring time M0781
Default values:
MD1 slave address
=
247
MD2 slave address
=
247
Baud rate
=
Auto
Parity/stop bit
=
Even, 1 stop bit
Monitoring time
=
15
seconds
Information
Parameter
MD2 slave address
is only available if AUMA redundancy I (option) is
available.
For further settings and information e.g. on redundancy, refer to Manual (Device
integration).
10.3.1.
Modbus TCP/IP gateway: set
Modbus TCP/IP gateway settings can be adapted by means of a web server.
Login password (default setting in the factory):
admin
59
SAEx 07.2 – SAEx 16.2 / SAREx 07.2 – SAREx 16.2 Control unit: electronic (MWG)
ACExC 01.2 Non-Intrusive Modbus TCP/IP
Commissioning (basic settings)