22.3 Setting ON and OFF times
ON and OFF times can be set independently of each other between 1 – 30
seconds at the 4 potentiometers R10 to R13.
Clockwise rotation:
Time extension
Counterclockwise rotation:
Time reduction
R10 (t-off)
: OFF time in direction OPEN
R11 (t-on)
: Running time in direction OPEN
R12 (t-off)
: OFF time in direction CLOSE
R13 (t-on)
: Running time in direction CLOSE
47
Multi-turn actuators SA 07.1 – SA 30.1/SAR 07.1 – SAR 30.1
Operation instructions
with actuator controls AUMA MATIC AM 01.1/AM 02.1
Figure 56: Cover plate for timer A1.6
R 10
R 11
R 12