Table 11: Example values for M25 size setting
Speed in % of the maximum motor speed
25 W
50 W
Output drive speed
in rpm
10 %
—
0.6
17 %
—
1
—
10 %
1.4
25 %
—
1.5
42 %
18 %
2.5
50 %
21 %
3
58 %
25 %
3.5
67 %
29 %
4
83 %
36 %
5
100 %
43 %
6
—
50 %
7
—
71 %
10
—
100 %
14
Table 12: Example values for M50 size setting
Speed in % of the maximum motor speed
25 W
50 W
Output drive speed
in rpm
10 %
—
0.3
17 %
—
0.5
—
10 %
0.6
33 %
17 %
1
50 %
25 %
1.5
83 %
42 %
2.5
100 %
50 %
3
—
58 %
3.5
—
67 %
4
—
83 %
5
—
100 %
6
Table 13: Example values for M100 size setting
Speed in % of the maximum motor speed
25 W
50 W
Output drive speed
in rpm
10 %
—
0.15
—
10 %
0.3
33 %
17 %
0.5
67 %
33 %
1
100 %
50 %
1.5
—
83 %
2.5
—
100 %
3
7.3.2.
Fieldbus
Signals
Feedback signals via fieldbus are defined by the GSD file.
Information
If required, download the GSD file (General Station Description) from the Internet:
www.auma.com
Refer to Technical data of the actuator for the Profibus DP ident no.
28
PROFOX / PF-M25 – PF-M100
Commissioning
Profibus DP