Manual drive for setting and emergency operation, handwheel does not rotate during electrical
operation.
Option: Handwheel lockable
Manual operation
AUMA plug/socket connector with screw-type connection
Connection to controls
Standard: Coupling without bore
Options: Machined coupling with bore and keyway, square bore or bore with two-flats accor-
ding to EN ISO 5211
Coupling
Dimensions according to EN ISO 5211
Valve attachment
For nominal voltage and 20 °C ambient temperature and an average load with running torque or modulating torque according to sepa-
rate technical data. The type of duty must not be exceeded.
1)
Technical data for limit and torque switches
2 x 10
6
starts
Mechanical lifetime
Silver plated contacts:
30 V AC/DC
U min.
250 V AC/DC
U max.
20 mA
I min.
5 A at 250 V (resistive load)
3 A at 250 V (inductive load, cos phi = 0.6)
I max. AC current
0.4 A at 250 V (resistive load)
0.03 A at 250 V (inductive load, L/R = 3 µs)
7 A at 30 V (resistive load)
5 A at 30 V (inductive load, L/R = 3 µs)
I max. DC current
Gold plated contacts:
5 V
U min.
30 V
U max.
4 mA
I min.
400 mA
I max.
Technical data for blinker transmitter
10
7
starts
Mechanical lifetime
Silver plated contacts:
10 V AC/DC
U min.
250 V AC/DC
U max.
3 A at 250 V (resistive load)
2 A at 250 V (inductive load, cos phi
≈
0.8)
I max. AC current
0.25 A at 250 V (resistive load)
I max. DC current
69
SGExC 05.1 – SGExC 12.1 Control unit: electromechanic
ACExC 01.2 Intrusive Modbus RTU
Technical data
Содержание AUMATIC ACExC 01.2
Страница 84: ...84 SGExC 05 1 SGExC 12 1 Control unit electromechanic Certificates ACExC 01 2 Intrusive Modbus RTU...
Страница 85: ...85 SGExC 05 1 SGExC 12 1 Control unit electromechanic ACExC 01 2 Intrusive Modbus RTU Certificates...
Страница 86: ...86 SGExC 05 1 SGExC 12 1 Control unit electromechanic ACExC 01 2 Intrusive Modbus RTU...
Страница 87: ...87 SGExC 05 1 SGExC 12 1 Control unit electromechanic ACExC 01 2 Intrusive Modbus RTU...