Figure 58:
Maintenance required
For further information, please also refer to <Corrective action>.
Failure (S0011)
The
S0011
indication shows the causes of the failure indication according to NAMUR
recommendation NE 107.
If such an indication has occurred, the display shows
S0011
:
●
the number of indications occurred
●
a blinking circle with a cross after approx. 3 seconds
Figure 59:
Failure
For further information, please also refer to <Corrective action>.
7.3
Mechanical position indicator/running indication
Mechanical position indicator:
●
Continuously indicates the valve position
(For a swing angle of 90°, the indicator disc [2] rotates by approximately 180°.)
●
Indicates whether the actuator is running (running indication)
●
Indicates that the end positions are reached (via indicator mark [3])
Figure 60:
Mechanical position indicator
[1]
Cover
[2]
Indicator disc
[3]
Mark
[4]
Symbol for position OPEN
[5]
Symbol for position CLOSED
41
SGExC 05.1 – SGExC 12.1 Control unit: electromechanic
ACExC 01.2 Intrusive Modbus RTU
Indications