13.
Technical data
Information
The following technical data includes standard and optional features. For detailed
information on the customer-specific version, refer to the order-relevant data sheet.
This data sheet can be downloaded from the Internet at http://www.auma.com in
German and English (indication of commission number required).
13.1.
Features and functions of actuator
Standard version (ATEX):
●
II2G Ex de IIC T4 (T3) Gb
●
II2G c IIC T4 (T3)
●
II2D Ex tb IIIC T130 °C (T190 °C) Db IP6x
Standard version (IECEx):
●
Ex de IIC T4 (T3) Gb
●
Ex tb IIIC T130°C (T190 °C) Db IP6x
For actual version, refer to actuator name plate.
Explosion protection
DEKRA 13 ATEX 0016 X
IECEx DEK 12.0080X
Ex certificates
●
Ex d flameproof enclosure:
-
Motor compartment
-
Switch compartment
-
Controls housing
-
Terminal compartment (for electrical connection: KES-Exd)
●
Ex e increased safety:
-
Terminal compartment (for electrical connection: KP, KPH or KES)
●
c constructional safety:
-
Gear housing
Type of protection
●
SQEx: Short-time duty S2 - 15 min
●
SQREx: Intermittent duty S4 - 25 %
Type of duty
1)
Refer to actuator name plate
Torque range
Refer to actuator name plate
Operating time for 90°
Standard: 3-ph AC asynchronous motor, type IM B9 according to IEC/EN 60034 Part 1
Motor
Refer to motor name plate
Permissible variation of mains voltage: ±10 %
Permissible variation of mains frequency: ±5 %
Motor voltage and frequency
Standard: F, tropicalized
Option: H, tropicalized
Insulation class
Standard: PTC thermistors (according to DIN 44082)
Option: Thermoswitches (NC) in the actuator and in the thermal overload relay of controls
Motor protection
Voltages: 110 – 120 V AC, 220 – 240 V AC or 400 V AC (externally supplied)
Power depending on the size 12.5 – 25 W
Motor heater (option)
Standard: Adjustable between 75° and
<
105°
Options: 15° to
<
45°, 45° to
<
75°, 105° to
<
135°
Swing angle
Self-locking
Part-turn actuators are self-locking, if the valve position cannot be changed from standstill
while torque acts upon the output drive.
Self-locking
Manual drive for setting and emergency operation, handwheel does not rotate during elec-
trical operation.
Option: Handwheel lockable
Manual operation
Indication whether manual operation is active/not active via switch (1 change-over contact)
Indication for manual operation
(option)
AUMA plug/socket connector with screw-type connection
Connection to controls
Standard: Coupling without bore
Options: Machined coupling with bore and keyway, square bore or bore with two-flats accord-
ing to EN ISO 5211
Coupling
Dimensions according to EN ISO 5211
Valve attachment
58
SQEx 05.2 – SQEx 14.2 / SQREx 05.2 – SQREx 14.2
Technical data
AMExC 01.1
Содержание AMExC 01.1
Страница 70: ...15 2 ATEX certificate 70 SQEx 05 2 SQEx 14 2 SQREx 05 2 SQREx 14 2 Certificates AMExC 01 1...
Страница 71: ...71 SQEx 05 2 SQEx 14 2 SQREx 05 2 SQREx 14 2 AMExC 01 1 Certificates...
Страница 72: ...72 SQEx 05 2 SQEx 14 2 SQREx 05 2 SQREx 14 2 Certificates AMExC 01 1...
Страница 73: ...73 SQEx 05 2 SQEx 14 2 SQREx 05 2 SQREx 14 2 AMExC 01 1 Certificates...
Страница 74: ...74 SQEx 05 2 SQEx 14 2 SQREx 05 2 SQREx 14 2 AMExC 01 1...
Страница 75: ...75 SQEx 05 2 SQEx 14 2 SQREx 05 2 SQREx 14 2 AMExC 01 1...