Exposed, rotating parts (discs/balls) at the valve!
Pinching and damage by valve or actuator.
→
End stops should be set by suitably qualified personnel only.
→
Never completely remove the setting screws [2] and [4] to avoid grease leakage.
→
Observe dimension T
min.
Information
●
The swing angle set in the factory is indicated on the name plate:
●
The setting sequence depends on the valve:
-
Recommendation for butterfly valves: Set end stop CLOSED first.
-
Recommendation for ball valves: Set end stop OPEN first.
Figure 25: End stop
[1]
Screw plug for end stop OPEN
[2]
Setting screw for end stop OPEN
[3]
Screw plug for end stop CLOSED
[4]
Setting screw for end stop CLOSED
14.2
12.2
10.2
07.2
05.2
Dimensions/sizes
23
23
20
17
17
T (for 90°)
12
13
12
11
11
T
min.
9.2.1.
End stop CLOSED: set
1.
Remove screw plug [3].
2.
Move valve to end position CLOSED with handwheel.
32
SQEx 05.2 – SQEx 14.2 / SQREx 05.2 – SQREx 14.2
Commissioning (basic settings)
AMExC 01.1
Содержание AMExC 01.1
Страница 70: ...15 2 ATEX certificate 70 SQEx 05 2 SQEx 14 2 SQREx 05 2 SQREx 14 2 Certificates AMExC 01 1...
Страница 71: ...71 SQEx 05 2 SQEx 14 2 SQREx 05 2 SQREx 14 2 AMExC 01 1 Certificates...
Страница 72: ...72 SQEx 05 2 SQEx 14 2 SQREx 05 2 SQREx 14 2 Certificates AMExC 01 1...
Страница 73: ...73 SQEx 05 2 SQEx 14 2 SQREx 05 2 SQREx 14 2 AMExC 01 1 Certificates...
Страница 74: ...74 SQEx 05 2 SQEx 14 2 SQREx 05 2 SQREx 14 2 AMExC 01 1...