6.2.2.
Actuator operation from remote
Risk of immediate actuator operation when switching on!
Risk of personal injuries or damage to the valve
→
If the actuator starts unexpectedly: Immediately turn selector switch to position
0 (OFF).
→
Check input signals and functions.
→
Set selector switch to position Remote control (REMOTE).
➥
Now, the actuator can be remote-controlled via fieldbus.
Information
For actuators equipped with a positioner, it is possible to change over between OPEN
- CLOSE control (Remote OPEN-CLOSE) and setpoint control (Remote SET-
POINT). For further information, please refer to the Manual (Operation and setting).
6.3.
Menu navigation via push buttons (for settings and indications)
Menu navigation for display and setting is made via the push buttons [1 – 4] of the
local controls.
Set the selector switch [5] to position 0 (OFF) when navigating through the menu.
The bottom row of the display [6] serves as navigation support and explains which
push buttons [1 – 4] are used for menu navigation.
Figure 47:
[1–4] Push buttons or navigation support
[5]
Selector switch
[6]
Display
48
SAVEx 07.2 – SAVEx 16.2 / SARVEx 07.2 – SARVEx 16.2 Control unit: electronic (MWG)
Operation
ACVExC 01.2 Non-Intrusive Modbus RTU