EMCY behaviour M0198
EMCY position M0232
Default value:
0.0 %
Setting range:
0.0 … 100.0 %
(from end position OPEN to CLOSED)
9.3.7.
EMERGENCY speed
Speed for an EMERGENCY operation.
Required user level:
Specialist (4)
or higher.
Customer settings M0041
EMCY behaviour M0198
Speed EMCY OPEN M1934
Speed EMCY CLOSE M2041
Default value:
6 (rpm)
Setting range:
6 ... 240 (rpm)
The adjustable speed range is indicated on the actuator name plate.
9.3.8.
Torque switching: by-pass
If an EMERGENCY operation is initiated, the torque switches can be by-passed
during this operation.
Required access level:
Specialist (4)
or higher.
Customer settings M0041
EMCY behaviour M0198
By-pass torque M0199
Default value:
Off
Setting values:
Off
No by-pass of the torque switching.
On
The signals of the torque switching in the actuator are by-passed.
9.3.9.
Motor protection: by-pass
If an EMERGENCY operation is initiated, the motor protection can be by-passed
during this operation.
Required user level:
Specialist (4)
or higher.
Customer settings M0041
EMCY behaviour M0198
Thermal by-pass M0200
Default value:
Off
Setting values:
Off
No by-pass of motor protection.
On
The signals of the thermoswitches or the PTC thermistors of the motor winding are
by-passed.
Information
It is not possible to by-pass the motor protection for actuators with explosion protec-
tion.
9.3.10.
Stepping mode: by-pass
If an EMERGENCY operation is initiated, stepping mode can be by-passed during
this operation.
Required user level:
Specialist (4)
or higher.
Customer settings M0041
EMCY behaviour M0198
90
Actuator controls
Failure functions
ACV 01.2/ACVExC 01.2 Profibus DP