Indication or setting either in percent
%
, Newton metre
Nm
or in pounds per
foot.
ft-lb
Read more
<Torque monitoring> chapter
7.2.1.
Torque switching: set
Once the set torque is reached, the torque switches will be tripped (overload protection
of the valve).
Information
The torque switches may also trip during manual operation.
Valve damage due to excessive tripping torque limit setting!
→
The tripping torque must suit the valve.
→
Only change the setting with the consent of the valve manufacturer.
Customer settings M0041
Torque switching M0013
Trip torque CLOSE M0088
Trip torque OPEN M0089
Default value: According to order data
Setting range: Torque range according to actuator name plate
Select main menu
1.
Set selector switch to position 0 (OFF).
2.
Press push button C
Setup
and hold it down for approx. 3 seconds.
➥
Display goes to main menu and indicates:
▶ Display
Select parameter
3.
Select parameter either:
→
click via the menu
to parameter, or
→
via direct display: press and enter ID
M0088
.
➥
Display indicates:
Trip torque CLOSE
CLOSE or OPEN
4.
Use
Up ▲ Down ▼
to select:
→
▶ Trip torque CLOSE
→
▶ Trip torque OPEN
➥
The black triangle
▶
indicates the current selection.
5.
Press
Ok
.
➥
Display shows the set value.
➥
The bottom row indicates:
Edit Esc
6.
Press
Edit
.
➥
Display indicates:
-
Specialist (4) →
continue with step 7
-
in bottom row
Up ▲ Down ▼ Esc →
continue with step 11
User login
7.
Use
Up ▲ Down ▼
to select user:
Information: Required user level:
Specialist (4)
or higher.
➥
The symbols have the following meanings:
-
black triangle:
▶
= current setting
-
white triangle:
▷
= selection (not saved yet)
8.
Press
Ok
.
➥
Display indicates:
Password 0***
38
Actuator controls
Basic settings for commissioning
ACV 01.2/ACVExC 01.2 Profibus DP