Save characteristics
3 characteristics can be saved.
Each characteristic consists of two charts (direction OPEN and direction CLOSE).
When saving, data is transferred from the buffer (RAM) to the read-only memory
(ROM).
Required user level:
Specialist (4)
or higher.
Asset Management M1231
Characteristics M0313
Torque-travel M1229
Save characteristic 1 M0652
Save characteristic 2 M0653
Save characteristic 3 M0654
15.3.2.
Position-time characteristic
Conditions
●
Actuator of the type range SA 07.2 – SA 16.2/SAR 07.2 – SAR 16.2
●
MWG position transmitter in actuator
Properties
During recording, the current position, for modulating actuators also the setpoint
position, within an adjustable time interval (between 1 second and 1 hour).
Application
By assessing the position-time characteristics, the control behaviour can be assessed
or insights on the use of the actuator can be gained.
Display position-time characteristics
Asset Management M1231
Characteristics M0313
Position-time M0806
Each characteristic has a designation:
ACTUAL-POSITION
= actual position
NOMINAL-POSITION
= setpoint position (modulating actuators only)
Use push buttons
Up ▲Down ▼
to change between characteristics.
Figure 60: Example of position-time characteristic
– – – 50 % (position between OPEN = 100 % and CLOSED = 0 %)
The following further information is saved with the characteristic (can be requested
via push button
Details
).
●
Saving date:
Time of last position measurement
●
Starting date:
Time of first position measurement
●
Scaling:
Y-axis (position)
Set resolution (time interval)
Actuator controls records 10,000 measured values. Set resolution of e.g. approx. 1
second (parameter
Interval position-time
= 1 [s] ) results in a recording time of 2.7
hours (10 000 seconds). Once this value has been exceeded, the former positions
will be overwritten (ring buffer)
Required user level:
Specialist (4)
or higher.
Asset Management M1231
138
Actuator controls
Asset Management
ACV 01.2/ACVExC 01.2 Profibus DP