Device configuration M0053
Service functions M0222
Import all parameters M0311
13.6.
Actual configuration: accept
When retrofitting controls, sub-assemblies are replaced by new sub-assemblies with
different functions.
Example: Replacing the PSU (different voltage).
If the controls detect a modified sub-assembly during start up, the following fault
signal is generated:
Configuration error
Accept current actual configuration
Accept new actual configuration as target configuration.
Required user level:
AUMA (6)
.
Device configuration M0053
Service functions M0222
Accept actual config. M0590
13.7.
Firmware update
A firmware update is required in the following cases:
●
Upgrade with new functions
●
Corrective actions
A firmware update can be performed in the following ways:
1.
via Bluetooth connection with AUMA CDT software
2.
via an SD card (card slot in local controls)
3.
via Profibus DP (e.g. using AUMA CDT)
Firmware version
The firmware version can be displayed via the following menu:
Device ID M0021
Version M0062
Firmware M0077
Firmware update via SD card
The menu
Update firmware
is only displayed if an SD card has engaged in the card
slot of the local controls.
Required access level:
Service (5)
or higher.
Device configuration M0053
Service functions M0222
Update firmware M0564
13.8.
Service software
Using the AUMA CDT software for Windows-based computers (notebooks or tablets)
and the AUMA Assistant App for Android-based devices, actuator data can be
uploaded and read, settings can be modified and stored. The connection between
computer and AUMA actuator is established wireless via Bluetooth interface. With
the AUMA Cloud, we provide an interactive platform to collect and assess e.g.
detailed device data of all actuators within a plant.
126
Actuator controls
Service functions
ACV 01.2/ACVExC 01.2 Profibus DP