Features and functions
Self-locking: Output speeds up to 90 rpm (50 Hz), 108 rpm (60 Hz)
NOT self-locking: Output speeds from 125 rpm (50 Hz), 150 rpm (60 Hz)
Multi-turn actuators are self-locking if the valve position cannot be changed from standstill while torque
acts upon the output drive.
Self-locking
Yes, multi-turn actuators are self-locking, if the valve position cannot be changed from standstill while
torque acts upon the output drive.
Self-locking
110 – 120 V AC, 220 – 240 V AC or 380 – 480 V AC (3-phase AC motors)
110 – 120 V AC, 220 – 240 V AC
Voltages:
Motor heater (option)
Power depending on the size 12.5 – 25 W
Manual drive for setting and emergency operation, handwheel does not rotate during electrical operation.
Manual operation
Handwheel lockable
Handwheel stem extension
Power tool for emergency operation with square 30 mm or 50 mm
Options:
Indication whether manual operation is active/not active via single switch (1 change-over contact)
Indication for manual operation (op-
tion)
B1 according to EN ISO 5210
Standard:
Valve attachment
A, B2, B3, B4, C, D according to EN ISO 5210
A, B, D, E according to DIN 3210
C according to DIN 3338
Options:
Special valve attachments: AF, AK, AG, B3D, ED, DD, IB1, IB3
A prepared for permanent lubrication of stem
Electromechanical control unit
Counter gear mechanism for end positions OPEN and CLOSED
Turns per stroke: 1 to 500 (standard) or 1 to 5,000 (option)
Limit switching
Single switch (1 NC and 1 NO) for each end position, not galvanically isolated
Standard:
Tandem switch (2 NC and 2 NO) for each end position, switches galvanically isolated
Triple switch (3 NC and 3 NO) for each end position, switches galvanically isolated
Intermediate position switches (DUO limit switching), adjustable for each direction of op-
eration
Options:
Torque switching adjustable for directions OPEN and CLOSE
Torque switching
Single switch (1 NC and 1 NO) for each direction, not galvanically isolated
Standard:
Tandem switch (2 NC and 2 NO) for each direction, switches galvanically isolated
Option:
Silver (Ag)
Standard:
Switch contact materials
Gold (Au), recommended for low voltage actuator controls
Option:
Potentiometer or 0/4 – 20 mA (electronic position transmitter)
Position feedback signal, analogue
(options)
Continuous indication, adjustable indicator disc with symbols OPEN and CLOSED
Mechanical position indicator
(option)
Blinker transmitter (for modulating actuator as an option)
Running indication
Self-regulating PTC heater, 5 – 20 W, 110 – 250 V AC/DC
Standard:
Heater in switch compartment
24 – 48 V AC/DC (for actuators with 3-phase AC/1-phase AC/DC motors)
or 380 – 400 V AC (for actuators with 3-phase AC motors)
Options:
A resistance type heater of 5 W, 24 V AC is installed in the actuator in combination with AMExC or
ACExC actuator controls
A resistance type heater of 5 W, 24 V AC is installed in the actuator in combination with ACExC actuator
controls.
85
SAEx 07.2 – SAEx 16.2/SAREx 07.2 – SAREx 16.2 Control unit - electromechanical
ACExC 01.2 Intrusive Profinet
Technical data