8.
Signals (output signals)
8.1.
Status signals via output contacts (digital outputs)
Characteristics
Output contacts are used to send status signals (e.g. reaching the end positions,
selector switch position, faults...) as binary signals to the control room.
Status signals only have two states: active or inactive. Active means that the
conditions for the signal are fulfilled.
8.1.1.
Assignment of outputs
The output contacts (outputs DOUT 1 – 12) can be assigned to various signals.
Required user level:
Specialist (4)
or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Signal DOUT 1 M0109
Table 26: Default values
Default value:
Output
Default value:
Output
Thermal fault
Signal DOUT 7
Fault
Signal DOUT 1
OPEN
Signal DOUT 8
End position CLOSED
Signal DOUT 2
Limit switch CLOSED
Signal DOUT 9
End position OPEN
Signal DOUT 3
Limit switch OPEN
Signal DOUT 10
Selector sw. REMOTE
Signal DOUT 4
Torque sw. CLOSED
Signal DOUT 11
Torque fault CLOSE
Signal DOUT 5
Torque sw. OPEN
Signal DOUT 12
Torque fault OPEN
Signal DOUT 6
8.1.2.
Coding the outputs
The output signals
Coding DOUT 1
–
Coding DOUT 12
can be set either to high
active or low active.
●
High active = output contact closed = signal active
●
Low active = output contact open = signal active
Signal active means that the conditions for the signal are fulfilled.
Required user level:
Specialist (4)
or higher.
Device configuration M0053
I/O interface M0139
Digital outputs M0110
Coding DOUT 1 M0102
Default values:
Coding DOUT 1
=
Low active
Coding DOUT 2
–
Coding DOUT 12
=
High active
8.2.
Analogue signals (analogue outputs)
Requirements
If the actuator is equipped with a position transmitter (potentiometer, RWG or EWG),
an analogue position feedback signal is available.
Valve position
Signal: E2 = 0/4 – 20 mA (galvanically isolated)
Designation in the wiring diagram: AOUT1 (position) AOUT2 (position)
For further information on this topic, please refer to Manual (Operation and setting).
64
SAEx 25.1 – SAEx 40.1 / SAREx 25.1 – SAREx 30.1
Signals (output signals)
ACExC 01.2
Содержание A 25.2
Страница 5: ...108 Index 111 Addresses 5 SAEx 25 1 SAEx 40 1 SAREx 25 1 SAREx 30 1 ACExC 01 2 Table of contents...
Страница 100: ...14 2 Actuator controls ACExC 01 2 KP KPH 100 SAEx 25 1 SAEx 40 1 SAREx 25 1 SAREx 30 1 Spare parts ACExC 01 2...
Страница 102: ...14 3 Actuator controls AUMATIC ACExC 01 2 KES 102 SAEx 25 1 SAEx 40 1 SAREx 25 1 SAREx 30 1 Spare parts ACExC 01 2...
Страница 104: ...14 4 Actuator controls ACExC 01 2 KT KM 104 SAEx 25 1 SAEx 40 1 SAREx 25 1 SAREx 30 1 Spare parts ACExC 01 2...
Страница 106: ...14 5 ExC wall bracket 106 SAEx 25 1 SAEx 40 1 SAREx 25 1 SAREx 30 1 Spare parts ACExC 01 2...
Страница 111: ...111...