3 CONFIGURATION AND COMMISIONING
Once made the needed connections, the elements and options used in the system
should be configured.
3.1
Power supply
Before activating system power, test previously service commuters that unable AC
source inputs and battery, see Illustration 3.
Connect the equipment to the electrical network. It should turn on correctly. The front
power indicator lights up and the firmware version will appear on the display during
startup. Then, the start screen will appear.
3.1.1 Install battery charger
The battery charger activation card must be installed, if available, before powering the
equipment.
The memory card includes the battery charging software. It is installed in the micro SD
(b) card connector . Move the metal part following the OPEN arrow and get up. Place the
card, lower the metal tab and move in the opposite direction LOCK to fix it. When the
equipment is turned on, the option to activate the charger and battery monitoring must
appear in the configuration menu.
3.2
Automatic Configuration. <Run Autosetup>
The automatic configuration function saves much of the configuration work of the ONE
system. The operation of the automatic configuration system makes the adjustments
according to what is detailed in the following sections. Any configuration can be
subsequently edited manually.
It is launched by pushing OK button in the option “Run AutoSetup” in the menu
Configuration/System/AutoSetup
This configuration verifies the elements follow EN54 requirements as described in the
following sections.
3.2.1 Date and time
The automatic system tests the configured date, if it is previous to 2010 it will ask the
user to adjust it manually.
3.2.2 Evacuation messages. Messages
System will ask the user if it wants to import messages,(only if USB memory is
connected) asking for the DATAxx directory to import them. Number xx is chosen
between 00 and 99.
Import folders are:
..\DATAxx\EVAC\ for evacuation.
..\DATAxx\ALERT\ for alert.
All the messages in each folder can be imported until the space is filled. Reproduction
order will be alphabetical. If the name coincides, the intern message is overwritten.
Important NOTE:
File names should have a maximum of 8 characters with no spaces
nor spCIEal characters (simbols) with the “.wav” extension.