PROGRAMMABLE PARAMETERS
9.14
20 Advanced
20A –
Tracking Gain
Range:
1% - 200%
Default:
50%
Description:
Fine-tunes the behaviour of the adaptive control algorithm.
20B –
Pedestal Detect
Range:
0% - 200%
Default:
80%
Description:
Adjusts the behaviour of the adaptive control algorithm for soft
stop.
20C –
Bypass Contactor Delay
Range:
50 – 200 milliseconds
Default:
100 milliseconds
Description:
Sets the starter to match the bypass contactor closing/opening
time. Set according to the specifications of the bypass contactor
used. If this time is too short, the starter will trip.
20D –
Model Rating
Range:
0020~0580
Default:
Model dependent
Description:
The soft starter’s internal model reference, as shown on the
silver label on the side of the unit (
).
M/R: 0085
Made in New Zealand
RoHS
18
59
5.
B
1
NOTE
This parameter can only be adjusted by authorised servicing agents.
20E –
Screen Timeout
Options:
1 minute (default)
4 minutes
2 minutes
5 minutes
3 minutes
Description:
Sets the timeout for the menu to automatically close if no
keypad activity is detected.
EMX4e User Manual (710-18433-00C) |
77