PROGRAMMABLE PARAMETERS
710-14888-00C EMX4i User Manual
91
8I –
Motor Temperature Flag
The EMX4i has a motor temperature flag to give early warning of abnormal
operation. The flag can indicate that the motor is operating above its normal
operating temperature but lower than the overload limit. The flag can signal the
situation to external equipment via one of the programmable outputs.
Range:
0% - 160%
Default:
80%
Description:
Sets the level at which the motor temperature flag operates, as
a percentage of the motor's thermal capacity.
8J –
Main Contactor Time
Range:
100 – 2000 milliseconds
Default:
400 milliseconds
Description:
Sets the delay period between the starter switching the main
contactor output (terminals 33, 34) and beginning the pre-start
checks (before a start) or entering the not ready state (after a
stop). Set according to the specifications of the main contactor
used.
9.13
9 Analog Output
9A –
Analog Output A
Options:
Current (% FLC)
(default)
Current as a percentage of motor full load
current.
Motor
Temperature (%)
The motor's temperature, calculated by the
thermal model.
Motor pf
Motor power factor, measured by the soft
starter.
Motor Power
(%kW)
Motor power, as a percentage of the
programmed power.
Heatsink
Temperature
(°C)
The soft starter's temperature, measured at
the heatsink.
Description:
Selects which information will be reported via the analog output.
9B –
Analog A Scale
Range:
0-20 mA
4-20 mA (default)
Description:
Selects the range of the analog output.
Содержание EMX4i