SETUP TOOLS
38
EMX4i User Manual 710-14888-00C
5.7
Auto-Start/Stop
The EMX4i can be configured to automatically start and/or stop the motor at a
particular time, or run it in cycles of a specified duration.
The Auto-Start/Stop option in Setup Tools gives quick access to the auto-start/stop
parameters.
1.
Press MENU to open the menu then select Setup
Tools.
2.
Scroll to Auto-Start/Stop and press the button.
3.
Scroll to the required function and press the
button.
Auto-Start/Stop
Start/Stop Mode
Start/Stop Sunday
Start/Stop Monday
4.
Adjust the settings as required:
Press the and buttons to select which
information to edit.
Use the and buttons to change the value.
Start/Stop Sunday
Start/Stop Disable
Start Time:
00:00
Stop Time:
00:00
5.
To save changes, press the button. The EMX4i will confirm the changes.
To cancel changes, press the button.
5.8
Network Address
To use the EMX4i on an Ethernet network, separate addresses must be configured
for:
•
IP Address
•
Gateway Address
•
Subnet Mask
To set the network addresses:
1.
Press MENU to open the menu then select Setup Tools.
2.
Scroll to Network Address and press the button.
3.
Scroll to the required function and press the button.
4.
The first digit of the address will be highlighted.
5.
Use and to select which digit to alter.
Use the and buttons to change the value.
6.
Press after the last digit to save the setting.
Set IP Address
192.168.000.002
When the action has been completed, the screen will
briefly display a confirmation message, then return to
the previous menu level.
Содержание EMX4i