PROGRAMMABLE PARAMETERS
710-14888-00C EMX4i User Manual
99
12T –
DHCP
Options:
Disable (default)
Enable
Description:
Selects whether the communications card will accept an IP
address assigned by DHCP.
NOTE
DHCP addressing is available with Modbus TCP and Ethernet/IP. DHCP
addressing is not supported with Profinet.
12U –
Location ID
Range:
0 - 65535
Default:
0
Description:
Sets the soft starter's unique location ID.
9.17
20 Advanced
20A –
Tracking Gain
Range:
1% - 200%
Default:
50%
Description:
Fine-tunes the behaviour of the adaptive control algorithm.
20B –
Pedestal Detect
Range:
0% - 200%
Default:
80%
Description:
Adjusts the behaviour of the adaptive control algorithm for soft
stop.
20C –
Bypass Contactor Delay
Range:
100 – 2000 milliseconds
Default:
150 milliseconds
Description:
Sets the starter to match the bypass contactor closing/opening
time. Set according to the specifications of the bypass contactor
used. If this time is too short, the starter will trip.
20D –
Model Rating
Range:
0020~0580
Default:
Model dependent
Description:
The soft starter’s internal model reference, as shown on the
silver label on the side of the unit (
).
M/R: 0085
Made in New Zealand
RoHS
18595.
B
1
NOTE
This parameter can only be adjusted by authorised servicing agents.