SYL-1512A PID TEMPEARATURE CONTROLLER INSTRUCTION MANUAL
Version 2.2, July. 2007
Auber Instruments, 730 Culworth, Alpharetta, GA 30022
www.auberins.com
e-mail: [email protected] Tel: 770-569-8420
WARNING
·Wiring precautions
-Install an external protection circuit if failure of this instrument could result in damage to your system.
-In order to prevent instrument damage or failure, protect the power line and the input/output lines from
high currents by using fuses with appropriate ratings. A very fast blowing fuse (such as an I
2
t fuse) is
needed when the output device is a solid-state relay (SSR). Please check with your fuse supplier for the
correct fuse for your SSR.
·Power supply
-Supply power of the specified rating.
-Do not turn on the power until all of the wiring is completed.
-Never use this instrument in the presence of inflammable gases or vapor.
-In order to prevent electric shock or burns, never touch the inside of the instrument.
-Do not attempt to modify this instrument.
·Maintenance
-Only authorized service engineers should replace parts.
-In order to use this instrument continuously and safely, conduct periodic maintenance. Some parts used
in this instrument have a limited service life and may deteriorate over time.
Caution
·Only clean the instrument when power is off.
·Please use a soft cloth or tissue to clean up stains on the display.
·Never use sharp & hard objects such as screwdrivers or ball pens to touch the buttons on the panel.
=============================================================
1. Features
◆
Compact size, 1/32 DIN that is only 24 x 48 x 75 mm (1x2 x3”)
◆
Supports 10 different types of commonly used temperature sensors, including Pt100 and Cu50 RTDs
,
T
、
R
、
J
、
B
、
S
、
K
、
E
、
and WRe3-WRe25 thermocouples.
◆
The PID control output can be configured by user for either relay contact or SSR.
◆
The relay contact output can also be configured as the alarm output, or on/off control
◆
Auto-tune function can automatically find the best PID parameters.
◆
Temperature can be displayed in Fahrenheit and Celsius.
◆
Can be used with either DC or AC power source.
Figure 1
2. Specification
◆
Power supply
:
85
~
260VAC or 85
~
360VDC
◆
Power consumption
:
<2W
◆
Sampling rate
:
4 sample/sec
◆
Accuracy
:
0.2% full scale
1