Sanitation Procedure

continue to run pump if water doesn’t flow.
B. The high level of chlorine required to sanitize

a water system is corrosive to most metals and

chlorine solution must not be allowed to remain in water

system more than 36 hours before being completely flushed

from system.
8. After  system  has  been  completely  flushed,  perform  a

bacteriological analysis on the water following all applicable

procedures.
NOTE:  Always follow the sanitizing procedure required by 

applicable state or local laws.
EPA Registered:  Well sanitizer pellets are EPA Registered 
for sanitizing potable water.  EPA Registration No. 50510-1
LARGE DIAMETER WELLS:  
Dug or bored wells should be disinfected in the same way 

as a drilled one.  Lower the water level as much as possible, 

remove the sand, silt and debris, and then treat with the 

chlorine solution.  Mix thoroughly by circulating the water 

back into the well  and use the hose to rinse the interior lining 

of the well. Do not try to disinfect an unprotected, unlined 

well because new seepage or surface contamination will flow 

into the water 

nearly as

 fast as you can disinfect it.  Disinfect 

the pipeline distribution system as indicated for drilled wells.
SPRINGS AND CISTERNS: 
Mix about ½ cup of household bleach in 5 gallons of water and 

use this to scrub the walls of the spring box or holding tank. 

With a constant flow of fresh water from the spring, there is 

probably no way of detaining the chlorine solution in the 

reservoir  for  more  than  a  few  minutes.   However,  the 

chlorinated  water  should  flow  through  the  pipeline  to 

disinfect the distribution system.  Cisterns can be disinfected 

in the same way but a source of clean water will be needed to 

flush the dirty waste out of the system.
For additional information about how to protect wells and 

springs and keep them from becoming contaminated, call or 

visit your local Cooperative Extension office, or your nearest 

certified water treatment specialist.
**TABLE 1  Quantity of solution mixed - 5.25% available 

chlorine (laundry bleach) for disinfecting   

wells, or 52,500 P.P.M..
WQA recommends 50mg/l or ppm chlorine concentration.

Formula: C2 X V2 / C1 = V1

C1= Household Bleach (52,500 P.P.M.) 

V1= Chlorine Amount Needed

C2= 50 mg/L 

V2= 80 gallons holding time

I.E.  50-ml/g X 80 gal= 4000/52,500= .08 gallons of chlorine (5.25%)

        .08 gal chlorine (5.35%) X 128 (oz/gal) = 10.24 oz (5.25%)

Dug Wells - 3 to 4 feet diameter - 4 cups per foot of water

Drilled Wells - 3 to 8 inch diameter - 1 cup per foot of water

HOW TO DISINFECT A WATER SYSTEM:
Every  new  well,  or  existing  water  supply  system  that 

has been disrupted for service or repair, should be 

disinfected before it is returned to use. Water in the 

well and storage tank should be treated with a strong  

chlorine solution to destroy disease organisms.  All pipelines 

and  fixtures  in  the  distribution  system  should  be  rinsed 

and flushed with chlorinated water.  Upon installation of 

a U.V. disinfection unit or yearly bulb replacement service, 

disinfection  with  chlorine  to  initially  flush  the  system  is 

recommended to assure line sanitation prior to U.V. start up.
The source of chlorine can be ordinary household liquid 

laundry  bleach  (about  5.25%  available  chlorine).    The 

quantity required depends on the volume of water to be 

treated.  The United States Environment Protection Agency 

(EPA) indicated that about 100 parts of chlorine, by weight, 

mixed in a million parts of water will destroy essentially all 

water-borne disease organisms.  Table 1 shows the quantity 

of liquid bleach required to disinfect wells of various 

diameters and depths.  
DISINFECTION PROCEDURE:

1.

Remove the cap or seal from the casing and measure

the depth of the water in the well, then refer to Table 

2

 to

determine how many chlorine pellets should be used.  In

some instances removing the seal to measure the water can

be a difficult task, and it is easier to estimate well and water

depth from well  log or other records.

2.

Remove well cap and determine if there is an unobstructed

path from the top of the well to the water level.  If it is not

possible to remove the well cap, remove vent or sanitation

access plug.

3.

Drop one pellet into the well and listen to hear if it hits the

water.  If the pellet hits the water, drop one-half the number

of pellets determined to be needed into the well.  These will

sink to the bottom and sanitize the lower part of the well.

4.

Mix the remaining pellets in a few gallons of water in a

CLEAN plastic container and pour the solution into the well.

5.

In order to mix the chlorine thoroughly throughout the

entire water system, it is necessary to recirculate the water in

the well.  This can be accomplished by connection a hose to

an out side faucet that is located after the pressure tank.  Use

hose to run water back down the well (this also rinses upper

portion of well).  After about 15 minutes of recirculation the

water, a strong chlorine odor should be apparent.  Turn off

hose.

6.

Bypass water softener and filters and open each water

outlet in the water system until chlorine is present in water.

This procedure assures that all the water in the system is

chlorinated.

7.

Allow the chlorinated water to stand in the system for

at least one (1) hour, and preferable overnight. After this,

open an outside faucet system until water runs chlorine free.

Repeat flush operation on each faucet in system.
NOTE:
A
. Chlorine may break loose iron deposits, slime and organic

material.  This material will make the water discolored.  The

material broken loose may plug pump screens.  Do not

GDS ©2019 • www.aquat.com

Содержание GDS-25

Страница 1: ...Installation Operation and Maintenance Manual CAUTION Read and Follow all safety rules and operating instructions before first use of product MODEL GDS 25 Ultraviolet Disinfection Systems Dealer Info...

Страница 2: ...GDS Series 2016 2...

Страница 3: ...tion Diagram 7 Electronic Controls Startup Procedures 8 Sample Screen Shots 9 Sanitation Procedure 10 11 Maintenance 12 Unit Parts Breakdown 13 Circuit Board Layout 14 Wiring Diagram 15 Troubleshootin...

Страница 4: ...y cause an unsafe condition 7 Intended for indoor use Do not install this disinfection system where it will be exposed to the weather Do not store this disinfection system where it will be exposed to...

Страница 5: ...rs cannot be maintained Flow rate must not exceed rated capacity of the unit The GDS series has a unique design with an ultraviolet germicidal lamp housed within a single quartz sleeve surrounded by a...

Страница 6: ...a vertical position in an enclosed area with good ventilation Allow clearance of at least the unit s length at one end for quartz sleeve and lamp replacement Four 4 anchor bolt holes are provided for...

Страница 7: ...GDS Series 2016 7 Installation Diagram GDS 2019 www aquat com...

Страница 8: ...ronic circuit board provides the latest in U V lamp monitoring technology U V LAMP CONTROL START UP PROCEDURE 1 Make sure the U V lamp is inserted per instructions into the quartz sleeve and U V chamb...

Страница 9: ...GDS Series 2016 9 Sample Screen Shots Fig 1 Fig 2 Fig 3 Fig 4 GDS 2019 www aquat com...

Страница 10: ...Water in the well and storage tank should be treated with a strong chlorine solution to destroy disease organisms All pipelines and fixtures in the distribution system should be rinsed and flushed wit...

Страница 11: ...isinfect the water if necessary Plumbing Line Sanitation Only When installing an ultraviolet disinfection system a prefilter with sump may serve as a source to sanitize the water lines only For whole...

Страница 12: ...the quartz sleeve through the stainless steel threaded nipples with 0 5 sticking out on each end Use a small amount of plumber s grease and install the o ring around the quartz sleeve Avoid riding the...

Страница 13: ...GDS Series 2016 13 Parts Breakdown GDS 25 GDS 2019 www aquat com...

Страница 14: ...GDS Series 2016 14 Circuit Board Layout GDS 2019 www aquat com...

Страница 15: ...GDS Series 2016 15 Wiring Diagram GDS 2019 www aquat com...

Страница 16: ...nstall a voltage regulator Check replace Replace Lamp Check output voltage Replace ballast Trace out and repair Leak at quartz nipple Defective or cracked o ring Replace o ring O Ring not seated prope...

Страница 17: ...additional three minutes 3 Open the sterile bottle or sterile container being used Holding the cap in a down position the operator should then hold his breath while taking the sample so as to avoid o...

Страница 18: ...GDS Series 2016 18 GDS 25 Specifications GDS 2019 www aquat com...

Страница 19: ...GDS Series 2016 19 Notes GDS 2019 www aquat com...

Страница 20: ...GDS Series 2016 20 Warranty GDS 2019 www aquat com...

Отзывы: