WIRING DIAGRAM

To conform with UL requirements, wires must be connected as shown in wiring diagram.

NOTE:  The maximum wire size that can be connected to this device is 18 Gauge!

Speaker 1                  Speaker 2

CAUTION: Do Not loop wires under screw terminals. Break wire run to provide supervision of connection. 

Installation must comply with all Building Codes and NFPA guidelines. Installation must adhere to N.E.C. 

and NFPA 70/72 wiring directives and comply with all National and Local Building Codes. 

APF-15U, APF-15TU, APF15TUC 

INSTALLATION INSTRUCTIONS

 

Specifications are subject to change without notice

 

www.AtlasSound.com

1601 JACK MCKAY BOULEVARD ENNIS, TEXAS U.S.A.   •    TELEPHONE: (800) 876-3332   •   FAX: (800) 765-3435

© 2005 ATLAS SOUND LP 

Printed in U.S.A. 

 000105  

ATS000702 RevE 01/05  

PN 8840400 

GENERAL DESCRIPTION

• Atlas Sound Models APF-15U, APF-15TU and APF-15TUC are high efficiency, U.L. Listed double re-entrant type loud     
  speakers. They comply with the requirements of UL Standard 1480, Fire Protective Signalling Speakers.
• They are designed to be used in conjunction with compatible control equipment for high intelligibility reproduction of 
  audible emergency and protective signals as well as voice messages.
• Model APF-15TUC includes a supervisory capacitor and is suitable for installation in systems employing supervised 
  circuitry (25V/70.7V). Maximum supervised circuit voltage is 24 VDC.
• For use in ambient ranges from -40˚C to 66˚C.

 

 

 

 

 

 

SPECIFICATIONS

POWER: 

             15 Watts RMS 

 

 

 

FREQUENCY RESPONSE:

   400-4,000Hz

SOUND LEVEL:

   103dB UL 10' Rating 

 (APF-15U Only) 

CONDUIT CONNECTION: 

    For 

1

2

" Conduit

Mounting Dimensions

To Next Speaker
or End of Line
Resistor

Power Tap Selector Switch

  Switch 

Impedance 

25V 

*db@ 

70V 

*db@

  Position 

 

Line 

10 Ft. 

Line 

10 Ft.

    

5.0 K 

 

.9 W 

  90

     2 

2.5 K 

           1.8 W 

  93

     3 

1.3 K 

.48 W 

  87       3.8 W 

  95

     4 

666 

.94 W 

  90        7.5 W          98

     5 

333 

1.8 W 

  93     15.0 W 

 100

     6 

89 

7.5 W 

  98           Do Not Use

     7 

45 

15.0 W 

 100          On 70 V.

* UL 3dB Increment Rating

6.12"

(155.5mm)

NOTE: Terminal #2 is the positive terminal

UL

CL

ASSIFIED

R

From 
Amplifier

Отзывы: