- 27 -
3.3
Installation
3.3.1
Indoor installation
If the machine is operated in a closed environment,
make sure that there is enough ventilation to remove
the exhaust gases from the room where the engine is
running; also ensure that the exhaust gases are
discharged at a distance that will not allow them to be
drawn back into the engine. Install an exhaust pipe of
sufficient diameter to duct the engine exhaust towards
the outside. Check for sufficient ventilation so that the
cooling air is not re-circulated.
Place the machine at least at 1m from each wall and
the ceiling and provide suitable openings to allow
sufficient air flow for adequate cooling and good
engine combustion.
3.3.2
Outdoor installation
– Place the light tower on a horizontal, even and
solid floor. Check the levels on top of the light
tower to ensure its level position.
– The light tower should be kept with the doors
closed, in order to avoid the ingress of water and
dust. Dust ingress reduces the lifetime of filters
and may reduce your light tower's performance.
– Check that the engine exhaust is not directed
towards people.
– Locate the rear end of the light tower upwind,
away from contaminated wind streams and walls.
Avoid re-circulation of exhaust air from the
engine. This causes overheating and engine power
decrease.
– Leave enough space for operation, inspection and
maintenance (at least 1 meter at each side).
– Check that the inner earthing system is in
compliance with the local legislation.
– Use PARCOOL EG for the engine cooling
system.
– Use a cable of suitable section to connect the PE
terminal to an earth plate that can ensure an earth
resistance suited to the characteristics of the light
tower.
– Check that the cable end of the earth pin is
connected to the earth terminal.
For more information about indoor
installation, consult your local Atlas
Copco dealer.
The light tower is wired for a TN-
system to IEC 364-3, i.e. one point in
the power source directly earthed -
in this case the neutral. The exposed
conductive parts of the electric
installation must be directly
connected to the functional earth.
00_00_HiLight H6+_EN.book Page 27 Friday, June 4, 2021 11:52 AM
Содержание HiLight H6+ DC
Страница 2: ...00_00_HiLight H6 _EN book Page 2 Friday June 4 2021 11 52 AM ...
Страница 93: ... 93 10 6 Dimensions ON ROAD UNDERCARRIAGE LED 00_00_HiLight H6 _EN book Page 93 Friday June 4 2021 11 52 AM ...
Страница 94: ... 94 ON ROAD UNDERCARRIAGE LED 00_00_HiLight H6 _EN book Page 94 Friday June 4 2021 11 52 AM ...
Страница 96: ... 96 00_00_HiLight H6 _EN book Page 96 Friday June 4 2021 11 52 AM ...
Страница 97: ... 97 Circuit diagrams 00_00_HiLight H6 _EN book Page 97 Friday June 4 2021 11 52 AM ...
Страница 112: ... 112 00_00_HiLight H6 _EN book Page 112 Friday June 4 2021 11 52 AM ...
Страница 115: ...00_00_HiLight H6 _EN book Page 115 Friday June 4 2021 11 52 AM ...
Страница 116: ...Printed in Spain www atlascopco com 00_00_HiLight H6 _EN book Page 116 Friday June 4 2021 11 52 AM ...