20/06/2011
PM 9845 0512 02
Page 20 of 36
6.6. Recovery water requirements for open water circuits
In open, non-recirculation water circuits, the main problems that are usually encountered relate to deposit control, corrosion
control and microbiological growth control. To minimize these problems, the water should meet a number of requirements.
Please contact Atlas Copco in case of doubt.
Recommended maxima (mg/l)
Closed water circuit
Open water circuit
Chloride (Cl
-
)
< 600
< 150
Sulphate (SO4
-
)
< 400
< 250
Total solids
< 3000
< 750
Suspended solids (as SiO
2
)
< 10
< 10
Free chlorine (Cl
2
)
< 4
< 2
Ammonia (NH
4+
)
< 0.5
< 0.5
Copper
< 0.5
< 0.5
Iron
< 0.2
< 0.2
Manganese
< 0.1
<0.1
Oxygen
< 3
< 3
Carbonate hardness (as CaCO
3
)
50-1000
50-500
Organics ( KMnO
4
Consumption)
< 25
< 10
Содержание ER S-1