Event log
The Qc1111™/Qc2111™ event log contains a list of
the last 15 recorded electrical trip or shutdown events
and the engine hours at which they occurred.
Once the log is full, any subsequent electrical trip or
shutdown alarm will overwrite the oldest entry in the
log. Hence, the log always contains the most recent
shutdown alarms. The module logs the alarm, along
with the engine running hours.
To view the event log:
1. Press the UP and DOWN buttons simultaneously
to display the navigation menu.
2. Once entered, cycle to the event log icon (1) and
enter.
3. To view the event log, repeatedly press the UP or
DOWN buttons until the LCD screen displays the
desired event.
4. Continuing to press the UP or DOWN buttons will
cycle through the past alarms.
5. To exit the event log, press the UP and DOWN
buttons simultaneously. The navigation menu will
be displayed.
4.2.2
Generator set operating modes
The generator set can be used in 3 operating modes:
– Stop/Reset mode,
– Automatic mode,
– Manual/Start mode
4.2.2.1
Stop mode
1. Activate Stop/Reset mode by pressing the STOP/
RESET button.
The Stop/Reset icon will be displayed on the
Qc1111™/Qc2111™ controller.
2. In Stop/Reset mode, the module will remove the
generator set from load (if necessary) before
stopping the engine, if it is already running.
If the engine does not stop when requested, the
FAIL TO STOP alarm is activated. To detect the
engine at rest the following must occur:
• Engine speed is zero as detected by the
CANbus ECU.
• Generator AC Voltage and Frequency must be
zero.
• Engine Charge Alternator Voltage must be
zero.
• Oil pressure sensor must indicate low oil
pressure
1
Icon to indicate that the event log is currently
displayed
2
Number of displayed event
3
Engine hours at which the event occurred
4
Icon to indicate the electrical trip or shutdown
alarm that has been recorded
5
Current operating mode of the module
3
4
5
1
2