2 .16
Configuration
of the Ambient probe
T55 or T58
-
To set the ambient probe and link it to
the correct heating zone:
-
Press for more than 3s the presence button
(item
11
,
). The ambient sensor
displays RU and a figure flashes.
-
Turn the knob to select the zone (1, 2).
If the installation is fitted with 2 ambient probes,
first connect one probe and parameter it to zone 2
then connect the other probe which is set by default
to zone 1 .
-
Press the presence button, the ambient probe will
display
P1
and a flashing number.
1
: Automatic
storage; correction of the reference value with the
button is adopted without any special validation
(timeout) or by pressing the operating level button.
2
: Save with confirmation; a correction of the value with
the knob is only adopted after pressing the operation
button.
-
Press the presence button, the ambient probe will
display
P2
and a flashing number.
0: OFF
; all operating parts are triggered.
1: ON
; the operating parts are locked:
- Switching the operation mode of the heating
circuit
- Adjusting the comfort value
- Changing the operating level
The ambient probe displays
OFF
for 3s when a locked
button is pressed.
2 .17
Configuration
of the central ambient unit (radio)
T75
- During commissioning, after initialising for around
3 minutes, the user language must be set:
-
Press the OK
OK
button.
-
Select the "user Interface" menu.
-
Select the language. Selection the language (English,
Deutsch,
Français
, Italiano, Nederlands, Español,
Português, Dansk).
T78
- refer to the instructions provided with the central
ambient unit radio.
"
When there are 2 heating circuits
-refer to the instructions provided with the central
ambient unit
Installation and operating manual
"
1605 - EN
"
- 35 -