background image

Version  number:  5025100811   

第  1  页  共  6  页 

Instruction Manual of ATL-982 Fire Display Panel 

 

------ Please read this Manual carefully before installing and using the product.    -----   

I. Product overview 

The ATL-982 fire display panel (display panel for short) is a kind of microprocessor-controlled fire display 
panel developed by our company. Each display panel is connected to a fire alarm control panel produced 
by our company via a special RS-485 interface to process and display the data sent from the fire alarm 
control panel. Each floor of a building may have a display panel installed. When there is a fire alarm on 
the floor where the display panel is installed, or the neighboring floor above or below it, the display panel 
will give a horn/strobe alarm and display the floor No., the room No., and some other position information 
of the fire alarm. 

II. Product features 

 

Each  display  panel  is  connected  with  a  fire  alarm  control  panel  via  a  RS-48  bus.  At  most  99 
display panels may be connected with each RS-485 bus. 

 

The display panels can display fire alarm messages or feedback messages only rather than fault 
messages, action messages or other messages.     

 

A fire alarm control panel may be used for setting the display area of a display panel.  The set 
display  panel  can  display  the  fire  alarm  messages  of  the  designated  area  (floor  display)  only. 
Note: See the User

’s Manual of the fire alarm control panel for the setting method. 

 

It can replace a JB-FSD-981 fire display panel in a 2100 system. 

III. Technical parameters   

1.

 

Executive standard: General Technical Conditions for Fire Indicating Panels (GB17429-1998) 

2.

 

Display  capacity:  Each  display  panel  can  display  the  fire  alarm messages  of  floors  -10~90 

and at most 99 fire alarm messages or feedback messages. 

3.

 

Wiring system: Four-wire system, power lines (+24V, GND) and RS485 signal lines (485A, 

485B) 

4.

 

 Operating environment: Indoor; temperature: -10

℃~

+50

; relative humidity: 

95% (40

without condensation) 

5.

 

Power supply: DC 24V 

±

20 % 

6.

 

Overall power consumption: 

3W 

7.

 

Contact  capacity:  Relay  dry  contacts,  normally  open  or  normally  closed,  capacity: 

1.25A/DC30V (resistive load) 

IV. Appearance and dimensions (see Fig.1) 

 

 

 

 

 

 

 

 

 

 

 

 

Fig.1 

Содержание ATL-982

Страница 1: ...y be connected with each RS 485 bus The display panels can display fire alarm messages or feedback messages only rather than fault messages action messages or other messages A fire alarm control panel may be used for setting the display area of a display panel The set display panel can display the fire alarm messages of the designated area floor display only Note See the User s Manual of the fire ...

Страница 2: ...ormally after startup The machine is operating normally as shown in Fig 4 will be displayed The current date and time are displayed at the top right corner of the screen The time is synchronous with that of the host machine of the fire alarm control panel and is refreshed by it there is some interval for refreshing The currently supported control system is displayed at the lower right corner of th...

Страница 3: ...Page 3 of 6 interface ...

Страница 4: ...ressed the fire alarm tone will be eliminated the MUTE indicator will be lit and the normally closed contact of the relay will be closed After receiving another fire alarm another horn strobe alarm signal may be triggered and the MUTE indicator will go out automatically Note After receiving a MUTE command from an automatic fire alarm control panel the display panel can also realize the muting func...

Страница 5: ...ch on the main board on the back of the display panel see Fig 2 for its location The JP3 dial switch has eight dial digits in all wherein the first to the seventh digits are used for setting the address see Fig 6 and Fig 7 and the eighth digit for choosing the 2100 control system or the 9000 control system If the JP3 dial switch is pulled to the ON position the 9000 control system will be chosen s...

Страница 6: ... the circuit of the equipment suffers short circuit open circuit wrong wiring and other defects The display panel is a precise electronic product and therefore needs to be managed by a specific person No other persons are allowed to operate it without permission Please wipe the surface of the equipment with alcohol VII Fault analysis and troubleshooting Fault phenomenon Possible cause Troubleshoot...