INSTALLATION INSTRUCTIONS
210-0197_Libretto_TX_ATI_2020-02_ATI-eng
11
ed. 2020-02
IMPORTANT:
follow the provisions laid down by national installation regulations.
14 INSTALLATION DEVICE BREAK-DRAFT DEFLECTOR
The device break-wind hood A is supplied not assembled. It should be fixed using the screws provided in the upper
part (B) of the device during installation.
For it is then connected to the conduit for the evacuation of exhaust fumes, which must be of a diameter not less than
the break-wind hood device (Ø 130 mm for mod. 160, Ø 180 mm for all other models) .
make sure the exhaust duct flue is not blocked
The part of the flue gas pipe connected to the break-wind hood device must also be vertical for at least 50 cm. Then
can be inserted a horizontal section, provided that the shortest possible and always maintaining a minimum slope
towards the appliance, so as not to obstruct the path of the fumes.
Mod. 160
Mod. 220/300/400/600/800
Make sure that during operation or transportation, the B flue safety thermostat bulb has not been damaged or
moved from its original position. It 'not tamper or disabled the flue safety device.
15 POSITION BULB THERMOSTAT FOR SAFETY SMOKE
The correct position of the bulb of the flue safety device is:
Mod. 160:
at a distance (C) mm 140 from the center of the appliance (75 mm from the outer edge),
in a position perpendicular to the radius and securely locked into bracket
Mod. 220/300/400: at a distance (C) of 282 mm from the center of the appliance (73 mm from the outer
edge), in a position perpendicular to the radius and firmly fixed into the bracket.
Mod. 600/800:
at a distance (C) mm 282 from the center of the appliance (178 mm from the outer
edge), in a position perpendicular to the radius and securely locked into bracket
The replacement of the fumes safety device must only be performed by qualified personnel and using the
original parts provided by the manufacturer.