D12
EX-IR
Gas Transmitter with IR Smart Sensor
Dec 2019 ( 85-0004 Rev A)
53
Figure 55. Alarm Inhibit Menu
Alarm Test Menu
The Alarm Test Menu can be used to test the gas level and Trouble alarms to
verify operation of the associated relays (see Relay Operation, Menus, and
Settings on page 72).
Note
Devices wired to the relays may activate when
“Start” is selected. Inform all personnel before
performing the test.
Figure 56. Alarm Test Menu
Display
Instructions
1.
Select Alarm
2.
Scroll up or down to specify which alarms to
test - C, W, A, T, and save the selection by
touching the Enter key.
3.
(C=Caution, W=Warning, A=Alarm, T=Trouble)
4.
Select Start to begin the test.
5.
Touch any key to end the test. The test stops
automatically after 5 minutes.
Test
Warning: this wi
►Alarm=
- - - -
Start
…Alarms >Test
Test
Warning: this wi
►Alarm=
- - A -
Start
…Alarms >Test
Test
Warning: this wi
Alarm= - - A -
>Start
…Alarms >Test
Test
Warning: this wi
Alarm= - - A -
Any key to STOP
…Alarms >Test
Test
Warning: this wi
►Alarm= C W A
T
Start
…Alarms >Test
“This will activate alarm relays”