Please note that even if the voltage drop allows certain amount of luminaries to be linked together,
too long chain of luminaries may affect the ability of the fuses in the electrical input to work properly
in a fault situation. Therefore it is not recommended to chain luminaries to a longer chain than 66 m
measured from the protective fuse (when the electrical supply is protected with C-curve fuse).
Please refer to local applicable laws and requirements for electrical installations.
The SLAM Star control gear protects itself against excessive voltage drops (numerous linking) by
switching itself off. If too many units are connected to the chain, some units of the chain will switch
off. You may start up by unplugging the last units on the line.