Slam®Hornet luminaires with LED modules: 
 

Supply 

voltage 

I

MAX

=16 A 

Recommended 

max. Load 

(max.80 %) 

Cable length 

Type of luminary 

Theoretical 

number of 

luminaries in 

series 

230 V 

2900 W 

5m 

CSHLED2 (50 

W) 

13 

110 V 

1400 W 

5m 

CSHLED2 (50 

W) 

13 

42 V 

500 W 

5m 

CSHLED2 (50 

W) 

10 

24 V 

300 W 

5m 

CSHLED2 (50 

W) 

 
Please  note  that  even  if  the  voltage  drop  allows  certain  amount  of  luminaries  to  be 
linked  together,  too  long  chain  of  luminaries  may  affect  the  ability  of  the  fuses  in the 
electrical input to work properly in a fault situation. Therefore it is not recommended to 
chain luminaries to a longer chain than 66m measured from the protective fuse (when 
the  electrical  supply  is  protected  with  C-curve  fuse).  Please  refer  to  local  applicable 
laws and requirements for electrical installations. 

The  Slam®Hornet  control  gear  protects  itself  against  excessive  voltage  drops  (numerous 
linking) by switching itself off. If too many units are connected to the chain, some units of the 
chain will switch off. You may start up by unplugging the last units on the line. 
 
Voltage  peaks  are  more  harmful  and  may  damage  the  control  gear  permanently  when 
subjected to excessive peaks continuously. 
 
If fluorescent tubes are flickering when the units are chained up, it may be due to excessive 
linking. This may shorten notably the lifetime of fluorescent tube. Unplug the last unit on the 
line to ensure proper function of the unit. 
 
 
 

4.

 

Inspection & Maintenance 

 

4.1 After use 

 
Take the following steps after the Slam®Hornet 

–unit has been taken out from Ex –area: 

 

1)  Clean the unit with a damp cloth (do not use detergents or solvents) 
2)  Change the anti-static film if only little light comes through it or it is damaged 
3)  Have a visual check on the unit (condition of cable, PC 

–tube, tightness of parts) 

4)  Let the unit dry in open air 

Содержание Slam Hornet 1 LED A

Страница 1: ...08 ATEX 066 or IECEx VTT 12 0009 Thank you for choosing Slam Hornet portable work light for your job site Purpose of this manual is to provide you all the necessary safety and product information to...

Страница 2: ...IA IIB or IIC in accordance with Equipment group IIA IIB or IIC 8 2 1 4 Temperature class of the equipment 9 2 1 5 Environmental criteria 9 3 Operating instructions 10 3 1 Personnel 10 3 2 Visual Insp...

Страница 3: ...et 2 LED Slam Hornet Linear 2x18W Slam Hornet Linear 2x36W Slam Hornet Linear 2 LED Dimensions mm Product model L Slam Hornet 1x18W 335 115 Slam Hornet 1x36W A Slam Hornet 1 LED A 540 115 Slam Hornet...

Страница 4: ...sion hazardous GASES D Certification taking account explosion hazardous DUSTS Explanation of marking for explosion hazardous area due to Gases e g Ex emb IIC T3 Gb Ex Certified for use in explosion ha...

Страница 5: ...ation or during expected malfunctions 1 3 Standard unit construction The following list familiarizes you with some common unit features important to recognize End parts Flexible plastic made end parts...

Страница 6: ...nts of own Socket Optional in built sockets receptacles for linking the Slam Hornet units in series apart from CSH118 Other common accessories Antistatic protective film for PC tube against chemical s...

Страница 7: ...5 ohm High voltage test electrical strength The purpose of this test is to measure leakage current trough insulation Vital test for revealing broken components or similar failures which can not be ide...

Страница 8: ...t category For explosion hazardous areas there are three equipment categories Category 1 product is suitable for use in Zones 0 1 and 2 20 21 and 22 Category 2 product is suitable for use in Zones 1 a...

Страница 9: ...ntioned in this instruction are Temperature Class T4 GASES Slam units with fluorescent tube and LED modules mentioned in this instruction are having maximum surface temperature of 90 C DUSTS 2 1 5 Env...

Страница 10: ...be used together with step down transformers Using Slam Hornet unit with transformers of 2 pole socket outlets without earthing bonding imposes certain extra requirements for the unit itself All the e...

Страница 11: ...king capacity of at least 1500 A Earth Leakage Circuit Breaker ELCB It is recommended to use a supply with 30 mA ELCB Please observe the type label for further data Luminaires for 110 VAC or 230 V sup...

Страница 12: ...is only for chaining Slam Hornet units 5 Fix them with accessories you have selected 6 Take the chain into Ex area Amount of lights which may be connected with each other depends on the supply voltage...

Страница 13: ...net control gear protects itself against excessive voltage drops numerous linking by switching itself off If too many units are connected to the chain some units of the chain will switch off You may s...

Страница 14: ...needed for measuring surface resistance of the PC tube 5 Maintenance instructions with exploded view diagram and spare parts list are available at your local distributor and the manufacturer Please wh...

Страница 15: ...Gas Atmospheres Please observe the requirements of the valid standards of the day Please study at least the following standards EN IEC 60079 14 Electrical installations in hazardous areas EN IEC 60079...

Страница 16: ...16 Helpdesk Under any doubt or question please contact your local distributor or the manufacturer Contact details Phone 358 20 734 3250 Fax 358 20 734 3299 Email info atexor com Web http www atexor c...

Отзывы: