Chapter 5. Outlet Access
41
General
When the
Configuration
page opens, the station’s
General
page is selected.
This page allows you to set up a power management configuration for the
device as a whole. The meanings of the field headings are given in the
following table:
Heading
Meaning
Device Name
To make things more convenient on a multi-station
installation, each station can be given a distinctive name.
To name a station key in the name of your choice - up to
15 letters and numbers.
Load Alarm
A checkmark in the check box disables an alarm from
being triggered when the device’s current load falls
outside of its specified range.
Environment Alarm
A checkmark in the check box disables an alarm from
being triggered when the device’s environment sensor
readings fall outside the fluctuation threshold settings.
See below.
Device Threshold Settings
These fields are used to set the maximum, minimum, and
fluctuation threshold settings. If a range falls below the
minimum setting, or exceeds the maximum setting an
alarm is triggered.
In order to keep alarms from being constantly triggered
due to slight fluctuations at the threshold points, you can
set a fluctuation range that must be exceeded when a
threshold is crossed in order for the alarm to be triggered.
Temperature Unit
Click a radio button to choose the temperature unit for the
temperature sensor.
Bank Threshold Settings
These fields are used to set the maximum, minimum, and
fluctuation threshold settings for the Banks. These
operate the same way as the Device Threshold Settings,
above.
Содержание PE7216r
Страница 28: ...eco PDU PE Series User Manual 18 Single Stage Installation Diagram Modem SA0142 DCE 7 5 1 3 2 4 6 ...
Страница 32: ...eco PDU PE Series User Manual 22 This Page Intentionally Left Blank ...
Страница 40: ...eco PDU PE Series User Manual 30 This Page Intentionally Left Blank ...
Страница 81: ...Chapter 7 Device Management 71 Security The Security page controls access to the eco PDU device ...
Страница 92: ...eco PDU PE Series User Manual 82 This Page Intentionally Left Blank ...
Страница 96: ...eco PDU PE Series User Manual 86 This Page Intentionally Left Blank ...