Chapter 1

Introduction

Overview

As part of its NRGence line, ATEN has developed a new generation of green 
energy power distribution units (PDUs) to effectively increase the efficiency of 
data center power usage. The NRGence PE5324LB / PE5324LG / PE5324LJ / 
PE5324LKJA / PE5324LJA / PE6324LB / PE6324LG / PE6324LJ / 
PE6324LJA / PE5340SLB / PE5340SLG / PE5340SLJ / PE5340SLJA eco 
PDUs are low profile intelligent PDUs that contain 24 or 40 AC outlets and are 
available in various IEC or NEMA socket configurations. The low profile 
series has a smaller input region on the PDU to provide more installation space 
for data centers. 

They provide secure, centralized, intelligent, power management (power on, 
off, cycle) of data center IT equipment (servers, storage systems, KVM 
switches, network devices, serial data devices, etc.), as well as the ability to 
monitor the center's health environment via sensors*. The basic characteristics 
of each model are shown in the table on page 3. 

NRGence eco PDUs offer remote power control combined with real-time 
power measurement - allowing you to control and monitor the power status of 
devices attached to the PDUs, either at the PDU device or outlet level, from 
practically any location via a TCP/IP connection. 

The power status of each outlet can be set individually, allowing users to switch 
each device On/Off. The eco PDU also offers comprehensive power analysis 
reports which can separate departments and locations, providing precise 
measurements of current, voltage, power and watt-hour in a real-time display. 

Installation and operation is fast and easy: plugging cables into their 
appropriate ports and user-friendly browser-based configuration and 
management is all that is entailed. Since the eco PDU firmware is upgradeable 
over the Net, you can stay current with the latest functionality improvements 
simply by downloading updates from our website as they become available.

NRGence eco PDU supports any 3rd party V1, V2, V3 SNMP Manager 
Software and NRGence eco Sensors (eco PDU Manager Software). eco 
Sensors provides you with an easy method for managing multiple devices, 
offering an intuitive and user-friendly Graphical User Interface that allows you 
to configure a PDU device and monitor power status of the equipment 
connected to it. 

Содержание eco PE Series

Страница 1: ...eco PDU PE Low Profile Series PE5324LB PE5324LG PE5324LJ PE5324LKJA PE5324LJA PE6324LB PE6324LG PE6324LJ PE6324LJA PE5340SLB PE5340SLG PE5340SLJ PE5340SLJA User Manual www aten com...

Страница 2: ...area is likely to cause harmful interference in which case the user will be required to correct the interference at his own expense The device complies with Part 15 of the FCC Rules Operation is subje...

Страница 3: ...consequential damages resulting from any defect in the software The manufacturer of this system is not responsible for any radio and or TV interference caused by unauthorized modifications to this dev...

Страница 4: ...ions and safety codes as well as deviations for breakers Only connect the PE Device to a grounded power outlet or a grounded system Make sure that the total current input of the connected systems does...

Страница 5: ...in shipping contact your dealer Read this manual thoroughly and follow the installation and operation procedures carefully to prevent any damage to the switch or to any other devices on the eco PDU i...

Страница 6: ...tribution 5 Remote Access 5 Operation 5 Management 5 Security 6 eco Sensors Energy Management Software 6 Requirements 7 Optional Accessories 8 Sensors 8 Cable Holders 8 Components 9 PE5324LB PE5324LG...

Страница 7: ...Logging In 35 The eco PDU Main Page 36 Page Components 37 Energy 38 Connections 38 Configuration 42 User 44 Administrator Information 44 User Information 45 Log 46 The System Log Event List 46 Notific...

Страница 8: ...ower Cables 71 Technical Support 72 International 72 North America 72 IP Address Determination 73 Specifications 75 PE5324LB PE5324LJ PE5324LG 75 PE5324LKJA PE5324LJA 76 PE6324LB PE6324LJ PE6324LG 77...

Страница 9: ...ult username and password Chapter 4 Browser Operation describes how to log in to the eco PDU with an internet browser and explains the layout and components of the eco PDU s user interface An Appendix...

Страница 10: ...bout all NRGence products and how they can help you save money in the data center visit NRGence on the Web or contact an ATEN Authorized Reseller Visit ATEN on the Web for a list of locations and tele...

Страница 11: ...surement allowing you to control and monitor the power status of devices attached to the PDUs either at the PDU device or outlet level from practically any location via a TCP IP connection The power s...

Страница 12: ...ost convenient most reliable and most cost effective way to remotely manage power access for multiple computer installations and allocate power resources in the most efficient way possible Note 1 Sens...

Страница 13: ...4A UL 30A Max PE6324LJ Yes 15A Max 12A UL 24A UL 30A Max PE6324LB Yes 15A Max 12A UL 24A UL 30A Max PE5324LG IEC 60309 32A 24 No 16A 10A 32A Max 30A TUV de rated PE6324LG Yes 16A 10A 32A Max 30A TUV d...

Страница 14: ...6 30P 40 40 x IEC320 C13 PDU Bank No 15A Max 12A UL 30A Max 24A UL de rated PE5340SLJ No 15A Max 12A UL 30A Max 24A UL de rated PE5340SLJA NEMA L5 30P 40 x NEMA 5 15R No 15A Max 12A UL 30A Max 24A UL...

Страница 15: ...er control via TCP IP and a built in 10 100 Ethernet port Network Protocols TCP IP UDP HTTP HTTPS SSL SMTP DHCP NTP DNS auto sense Ping eco PDU Power Management software eco Sensors Supports SNMP Mana...

Страница 16: ...on an outlet by outlet basis Event logging and syslog support Upgradeable firmware Multilanguage support English Traditional Chinese Simplified Chinese Japanese German Italian Spanish French Russian K...

Страница 17: ...ing of attached computers the computer s BIOS must support Wake on LAN or System after AC Back For Safe Shutdown The computer must be running Windows Windows 2000 or higher or Linux The Safe Shutdown...

Страница 18: ...art Higher sensor installation density is helpful to generate more accurate data Available sensors are show in the table below Sensor Management Sensors can be managed via the eco PDU s built in graph...

Страница 19: ...Chapter 1 Introduction 9 Components PE5324LB PE5324LG PE5324LJ Front View 1 5 6 2 3 3 3 4 7 4 4...

Страница 20: ...he circuit breakers will trip Push the switch back to recover normal operation 3 Power Outlets 3 x IEC 320 C19 4 21 x IEC 320 C13 5 Sensor Ports External sensors plug into these two RJ 11 ports 6 LAN...

Страница 21: ...Chapter 1 Introduction 11 PE5324LKJA Front View 1 4 5 6 4 4 2 3 7 3 3...

Страница 22: ...k Bank 1 1 8 x NEMA 5 15R Twist Lock Bank 1 2 8 x NEMA 5 15R Twist Lock Bank 2 8 x NEMA 5 15R Twist Lock 4 Bank Power LED These three LEDs indicate the PDU s bank power status Lights red to indicate t...

Страница 23: ...Chapter 1 Introduction 13 PE5324LJA Front View 1 4 5 2 3 6 3 3...

Страница 24: ...recover normal operation 3 Power Sockets 24 in total 24 x NEMA 5 15R Bank 1 1 8 x NEMA 5 15R Bank 1 2 8 x NEMA 5 15R Bank 2 8 x NEMA 5 15R 4 Sensor Ports External sensors plug into these two RJ 11 po...

Страница 25: ...Chapter 1 Introduction 15 PE6324LB PE6324LG PE6324LJ Front View 1 5 8 6 8 8 7 2 3 3 3 4 4 4...

Страница 26: ...ver normal operation 3 Power Sockets 3 x IEC 320 C19 4 21 x IEC 320 C13 5 Sensor Ports External sensors plug into these two RJ 11 ports 6 LAN Port and LEDs The cable that connects the eco PDU to the L...

Страница 27: ...Chapter 1 Introduction 17 PE6324LJA 1 4 7 5 7 7 6 2 3 3 3...

Страница 28: ...ation 3 Power Sockets 24 x NEMA5 15R 4 Sensor Ports External sensors plug into these two RJ 11 ports 5 LAN Port and LEDs The cable that connects the eco PDU to the LAN plugs in here The Link and LAN L...

Страница 29: ...Chapter 1 Introduction 19 PE5340SLB PE5340SLG PE5340SLJ Front View 1 4 5 6 2 3 3...

Страница 30: ...trip Push the switch back to recover normal operation 3 Power Sockets 40 in total 40 x IEC320 C13 Bank1 Outlet 1 20 20 x C13 Bank2 Outlet 21 40 20 x C13 4 Sensor Ports External sensors plug into these...

Страница 31: ...Chapter 1 Introduction 21 PE5340SLJA Front View 1 4 5 6 2 3 3...

Страница 32: ...R Bank1 Outlet 1 20 20 x NEMA 5 15R Bank2 Outlet 21 40 20 x NEMA 5 15R 4 Sensor Ports External sensors plug into these two RJ 11 ports 5 LAN Port and LEDs The cable that connects the eco PDU to the LA...

Страница 33: ...e the selection between the items 3 Selection Pushbutton Press this button to cycle the selection through the items the LEDs next to the items indicate which one the display relates to 4 Reset Switch...

Страница 34: ...the selection between the items When a sensor is plugged in the sensor LED lights up 4 Selection Pushbutton Press this button to cycle the selection through the items the LEDs next to the items indica...

Страница 35: ...of the back panel or the top and bottom ends of the device as shown in the diagram below Note The eco PDU model shown in the diagram is for rack mounting reference only 1 Important safety information...

Страница 36: ...Placement For safety reasons the eco PDU should not be installed with the power sockets facing directly up or down and thus should only be installed with the power sockets facing out from a vertical...

Страница 37: ...ort 3 If you are using sensors in your eco PDU installation connect them to the sensor ports on the unit s front panel Note Sensors are optional Please see Optional Accessories page 8 and the detailed...

Страница 38: ...eco PDU PE Low Profile Series User Manual 28 3 2 1 4 1...

Страница 39: ...U unit Secure the cable holders using the specially designed holes around the individual power outlets as shown below Note 1 Cable holders are an optional accessory See Cable Holders page 8 2 Use only...

Страница 40: ...ou use a tie wrap to secure the sensor tighten the tie wrap over the recessed channel on the sensor as shown in the following diagram Note 1 The sensors shown in the above diagram are for reference pu...

Страница 41: ...er from any platform See First Time Setup page 32 and the following sections in this chapter for full details eco Sensors All eco PDUs support eco Sensors eco PDU Manager Software NRGence eco Sensors...

Страница 42: ...er Note 1 Since this is the first time you are logging in use the default Username administrator and the default Password password For security purposes we recommend changing them to something unique...

Страница 43: ...n To set up the network do the following 1 Click the Setup tab 2 The interface displays the Device Configuration page A screen similar to the one below appears 3 Fill in the IPv4 Configuration fields...

Страница 44: ...nformation section reset the name and password fields to something unique then click Save at the bottom of the page Note If you forget the Administrator s name or password short the mainboard jumper t...

Страница 45: ...You can get the IP address from the eco PDU administrator or see IP Address Determination page 73 for information about setting it up yourself 2 If a Security Alert dialog box appears accept the certi...

Страница 46: ...ge After you have successfully logged in the eco PDU Main Page comes up with the Outlet Access Connections page displayed Note The screen depicts an Administrator s page Depending on a user s type and...

Страница 47: ...that pertain to the item selected in the tab bar The items that appear in the menu bar are determined by the user s type and the authorization options that were selected when the user s account was cr...

Страница 48: ...ccess tab and the Connections menu The contents of the PDU Status and Outlet Status sections are displayed in the main panel Note Only enabled eco PDU models will display the Outlet Status submenu sec...

Страница 49: ...ceeds the maximum setting an alarm is triggered Breaker status ON OFF displays here Voltage Frequency is displayed here in Hz On Off Reboot You can manually turn the device On and Off from this page b...

Страница 50: ...elds are used to set the maximum minimum and fluctuation threshold settings for Current Voltage Power and Power Dissipation If a range falls below the minimum setting or exceeds the maximum setting an...

Страница 51: ...witching as described on this page On Off Reboot You can manually turn the outlet On and Off from this page by clicking the radio buttons To Reboot the outlet enable the Reboot checkbox and click on S...

Страница 52: ...ounds an alarm and sends SNMP trap or e mail alerts when a circuit breaker trips or a PDU Bank threshold setting exceeds the minimum or maximum setting Outlet Configuration The Outlet Configuration se...

Страница 53: ...t is turned On the eco PDU waits for the amount time set in the Power On Delay field then sends an Ethernet message to the computer connected to the Outlet telling the computer to turn itself On Note...

Страница 54: ...in sessions 2 The eco PDU supports a total of 3 concurrent login sessions Administrator Information This section is used to set the Administrator name and password Only Administrators can view this se...

Страница 55: ...ment The Management field allows you to Enable or Disable a user s account Enable stores the user account see User Information page 45 Disable disables the user account Name From 1 to 16 characters ar...

Страница 56: ...to date with the latest events The entry box to the right of the Refresh button lets you set the number of events to display per page Simply key in the number of your choice The top right of the main...

Страница 57: ...ry item rows have a white background Click the checkboxes under the column headings to select which component s will receive notification of the log events Clicking on a main category heading s row au...

Страница 58: ...em Meaning PDU Name This field lets you give the device a unique name Simply delete whatever is in the text box and key in the name of your choice Click Save located at the bottom of the page to save...

Страница 59: ...not be found Select whether to allow only secure browser logins as show below An explanation of the fields is given in the table below Note 1 Valid entries for all of the Service Ports are from 1 6553...

Страница 60: ...e Obtain DNS Server address automatically radio button To specify the DNS Server address manually select the Set DNS server address manually radio button and fill in the addresses for the Preferred an...

Страница 61: ...ct the Use DHCPv6 to obtain DNS Server Addresses radio button To specify the DNS Server address manually select the Set DNS server address manually radio button and fill in the addresses for the Prefe...

Страница 62: ...key in the IP address of your SMTP server 2 If your server requires authentication put a check in the My server requires authentication checkbox 3 Key in the appropriate account information in the Ac...

Страница 63: ...use 3 Key in the IP address es and the service port number s of the computer s to be notified of SNMP trap events The valid port range is 1 65535 The default port number is 162 Note Make sure that th...

Страница 64: ...all the events that take place on eco PDU devices and write them to the eco PDU Syslog server do the following 1 Check Enable Syslog Server 2 Key in the IP address and the port number of the Syslog s...

Страница 65: ...U time parameters Time Zone To establish the time zone that the eco PDU is located in drop down the Time Zone list and choose the city that most closely corresponds to where it is at If your country o...

Страница 66: ...its date and time settings from the locally connected PC Network Time To have the time automatically synchronized to a network time server do the following 1 Check the Enable auto adjustment checkbox...

Страница 67: ...t are permitted from a remote user Timeout sets the amount of time a remote user must wait before attempting to login again after exceeding the number of allowed failures Working Mode If ICMP is enabl...

Страница 68: ...16 Minimum Password Length Sets the minimum number of characters required for a password Acceptable values are from 1 16 Password Must Contain At Least Checking any of these items requires users to i...

Страница 69: ...168 0 126 abcdefg The following characters are allowed 0 9 a z A Z _ The following characters are not allowed Space Compound characters etc Note 1 There must be a forward slash between the IP address...

Страница 70: ...dresses within the filter range are allowed access all other addresses are denied access If the exclude button is checked all the addresses within the filter range are denied access all other addresse...

Страница 71: ...r s IP address is allowed by the IP filter but its MAC address is excluded by the MAC filter then that computer s access is blocked In other words if either filter blocks a computer then the computer...

Страница 72: ...lternate RADIUS servers The default port number for the Preferred server is 1812 the default port number for the Alternate server is 1645 Note Make sure that the port numbers you specify here match th...

Страница 73: ...o use your own private encryption key and signed certificate rather than the default ATEN certificate There are two methods for establishing your private certificate generating a self signed certifica...

Страница 74: ...s located and select it 2 Click Browse to the right of Certificate browse to where your certificate file is located and select it 3 Click Upload to complete the procedure Note 1 Clicking Restore Defau...

Страница 75: ...re level is compared with that of the upgrade file If the current version is equal to or higher than the upgrade version a popup message appears to inform you of the situation and stops the upgrade pr...

Страница 76: ...to inform you of the situation and stops the upgrade procedure If you didn t enable Check Main Firmware Version the upgrade file is installed without checking what its level is Once the upgrade comple...

Страница 77: ...sks what you want to do with the file select Save to disk then save it in a convenient location Restore To restore a previous backup do the following 1 Click Browse navigate to the file and select it...

Страница 78: ...eco PDU PE Low Profile Series User Manual 68 This Page Intentionally Left Blank...

Страница 79: ...ided Never spill liquid of any kind on the device Unplug the device from the wall outlet before cleaning Do not use liquid or aerosol cleaners Use a damp cloth for cleaning The device should be operat...

Страница 80: ...us voltage points or short out parts resulting in a risk of fire or electrical shock Do not attempt to service the device yourself Refer all servicing to qualified service personnel If the following c...

Страница 81: ...rack load should not exceed 80 percent of the branch circuit rating Make sure that all equipment used on the rack including power strips and other electrical connectors is properly grounded Ensure tha...

Страница 82: ...on ready beforehand Product model number serial number and date of purchase Your computer configuration including operating system revision level expansion cards and software Any error messages displa...

Страница 83: ...ork address See Setup page 48 Method 1 For computers running Windows an IP address can be determined and or assigned with the IP Installer utility The utility can be obtained from the Download area of...

Страница 84: ...the program Method 2 1 Set your computer s IP address to 192 168 0 XXX Where XXX represents any number or numbers except 60 192 168 0 60 is the default address of the eco PDU 2 Specify the device s de...

Страница 85: ...ge Green Link 1 Green Sensor 2 Green Switches Reset 1 x Semi recessed Pushbutton Power 2 x 16A Slim Breaker Button 1 x Pushbutton I P Rating 100 240V 50 60Hz 24A UL 30A Max 100 240V 50 60Hz 32A Power...

Страница 86: ...ess 3 digit 7 segment Orange Power 1 Blue LAN 10 100M 1 Orange Green Link 1 Green Sensor 2 Green Bank Power Indicator 3 Red Switches Reset 1 x Semi recessed Pushbutton Power 2 x 16A Slim Breaker Butto...

Страница 87: ...nge Green Link 1 Green Sensor 2 Green Switches Reset 1 x Semi recessed Pushbutton Power 2 x 16A Slim Breaker Button 1 x Pushbutton I P Rating 100 240V 50 60Hz 24A UL 30A Max 100 240V 50 60Hz 32A Power...

Страница 88: ...segment Orange Power 1 Blue LAN 10 100M 1 Orange Green Link 1 Green Sensor 2 Green Outlet Status 24 Orange Switches Reset 1 x Semi recessed Pushbutton Power 2 x 16A Slim Breaker Button 1 x Pushbutton...

Страница 89: ...t 1 x Semi recessed Pushbutton Power 2 x 16A Slim Breaker Button 1 x Pushbutton I P Rating 100 240V 50 60Hz 30A Max 24A UL de rated 100 240V 50 60Hz 32A Power Capacity 6240 VA Max 4992 VA UL de rated...

Страница 90: ...egment Orange Power 1 Blue LAN 10 100M 1 Orange Green Link 1 Green Sensor 2 Green Switches Reset 1 x Semi recessed Pushbutton Power 2 x 16A Slim Breaker Button 1 x Pushbutton I P Rating 100 120V 50 60...

Страница 91: ...ou can clear the login information with the following procedure 1 Power off the eco PDU and remove its housing 2 Short the jumper labeled J3 PIN10 and PIN9 3 Power on the eco PDU 4 After the beep indi...

Страница 92: ...nce connection to improper equipment or attempted repair by anyone other than ATEN This warranty does not cover products sold AS IS or WITH FAULTS IN NO EVENT SHALL ATEN S LIABILITY EXCEED THE PRICE P...

Отзывы: