IDA8 Global-Net User Manual
86
© 2017, ATEÏS, member of PAX ProAV Group
"Zone n BackUp AMP Rating too low" (where n = 1~8)
A text message displays at the window [Machine Fault Record] in Ateis Studio:
A buzzing sound outputs to the monitoring speaker on the front panel of the IDA8C.
Troubleshooting: Check the amplifier power and wiring. Once it's recovered, the LOG will show:
"Zone n Normal AMP OK"
"Zone n Backup AMP OK"
3.1.9.1.22 BackupAmp Used State
A normal amplifier has failed and was replaced by the backup amplifier.
Indication:
LED Indicator: When this error is detected, the following LEDs will light up:
o
G. Fault LED on the front panel of the IDA8C/S.
Log:
The text messages display at the touch screen of the IDA8C:
"BackupAmp Used State"
"Machine X Zone Y Use Backup Amp Z" (Where X = machine ID, Y = 1~8 and Z = 1~n).
A text message displays at the window [Machine Fault Record] in Ateis Studio:
A buzzing sound outputs to the monitoring speaker on the front panel of the IDA8C.
Troubleshooting: Check the normal amplifier power and wiring.
3.1.9.1.23 Local AteisNet Backup Mode
One of the local ATEIS net port has broken.
Indication:
LED Indicator: When this error is detected, the following LEDs will light up:
o
G. Fault LED on the front panel of the IDA8C/S.
Log:
A text message displays play at the touch screen of the IDA8C:
"Local AteisNet Backup Mode"
A text message displays at the window [Machine Fault Record] in Ateis Studio:
A buzzing sound outputs to the monitoring speaker on the front panel of the IDA8C.
Troubleshooting: Check the ATEIS Net cable.