CHAPTER 3. EQUIPMENT ROOM DESIGN
site/satellite location or adapter. Staggered-finger cables are
recommended for all multiple 25-pair station cables.
Staggered-finger cables are available in both double-ended and
single-ended types.
●
●
●
Bulk Cable—This cable is the same as the connectorized 25-pair
cable or multiple 25-pair cable; however, the bulk cable is not
equipped with connectors. Use this cable between the equipment
room and satellite closets when both are equipped with
punch-down type terminal/connecting blocks.
Nonconnectorized 4-pair station cable—Use this cable when
4-pair station cables are to be field-terminated on the 110-type
terminal blocks/66-type connecting blocks in the equipment room
or satellite closet and the information outlets require push-on
connections.
Single modular plug-ended 4-pair station cable(Figure 3-60)—Use
this cable between adapters and information outlets that require
push-on connections. It can also be used when 4-pair station
cables are field-terminated on the 110-type terminal
blocks/66-type connecting blocks in the equipment room or
satellite closet and modularly connected to information outlets.
The station cables are available in the following lengths:
●
●
●
●
●
●
●
10 feet
25 feet
50 feet
75 feet
100 feet
150 feet
200 feet.
●
Double modular plug-ended 4-pair station cable—Use this cable
to provide nonstandard length runs between adapters and
information outlets with push-on connections. It can also be used
between adapters and modularly connected information outlets. It
is available in the same lengths as the single modular plug-ended
cable (see Note).
3-92
Содержание System 75
Страница 1: ...AT T AT T System 75 and System 75 XE Wiring...
Страница 2: ...AT T AT T System 75 and System 75 XE Wiring 555 200 111 Issue 2 August 1989...
Страница 16: ...System Wiring Figure 1 2 System Uniform Wiring Plan 1 7...
Страница 17: ...CHAPTER 1 INTRODUCTION Figure 1 3 Sample Uniform Wiring Installation 1 8...
Страница 29: ...CHAPTER 2 HARDWARE 66 110 Type Figure 2 1 Block Diagram of System 75 or 75 XE Installation 2 2...
Страница 35: ...CHAPTER 2 HARDWARE 66 110 Type Figure 2 4 110A Type 100 Pair Terminal Block 2 8...
Страница 36: ...110 Type Hardware Description Figure 2 5 110A Type 300 Pair Terminal Block 2 9...
Страница 98: ...Typical System Equipment Room Floor Plans 3 15...
Страница 143: ...CHAPTER 3 EQUIPMENT ROOM DESIGN 3 60...
Страница 144: ...Equipment Room Hardware And Cabling Installation 3 61...
Страница 162: ...Equipment Room Hardware And Cabling Installation 3 79...
Страница 163: ...Equipment Room Hardware And Cabling Installation 3 80...
Страница 197: ...Tables Table 4 A Recommended Protectors 4 42 v...
Страница 203: ...CHAPTER 4 STATION WIRING Figure 4 4 3 Pair to 4 Pair Wiring Labeling From Equipment Room to Information Outlet 4 6...
Страница 205: ...CHAPTER 4 STATION WIRING Figure 4 5 4 Pair Station Wiring Labeling From Equipment Room to Information Outlet 4 8...
Страница 212: ...Adjunct Powering 4 15...
Страница 214: ...Adjunct Powering 4 17...
Страница 216: ...Patch Cord Jumper Installation And Administration 4 19...
Страница 241: ...CHAPTER 4 STATION WIRING 4 44...
Страница 244: ...Miscellaneous Wiring Installation 4 47...
Страница 246: ...Miscellaneous Wiring Installation 4 49...
Страница 252: ...Miscellaneous Wiring Installation 4 55...
Страница 254: ...Miscellaneous Wiring Installation 4 57...
Страница 277: ...CHAPTER 5 AUXILIARY EQUIPMENT INSTALLATION Figure 5 1 Connections for Loudspeaker Paging and Music on Hold 5 4...
Страница 314: ...CHAPTER 5 AUXILIARY EQUIPMENT INSTALLATION 5 41...
Страница 324: ...CHAPTER 5 AUXILIARY EQUIPMENT INSTALLATION 5 51...