Features 

 

Real time detect, transmit and control indoor air quality 

 

3-color TFT screen display and warning indoor CO2, TVOC, temperature and 

relative humidity 

 

Four buttons for operation conveniently 

 

Two power supply optional for different application 

 

Provide up to 3 a 1 relay outputs or 3  1 analog outputs 

 

Optional Modbus RS485 interface, to connect PC, realize remote control 

 

Specification 

Carbon Dioxide 

Detecting gas 

Carbon Dioxide (CO2) 

Gas sensor 

NDIR sensor 

Accuracy@25

(77

±50ppm + 3% reading

 

or ±75ppm (whichever is greater) 

Stability 

<2% of FS over lifetime (15 years) of sensor 

Calibration 

ABC Logic

 

self-calibration 

Lifetime of NDIR CO2 sensor 

15 years (normal using) 

Response time 

<2 minutes for 90% step change 

Renewed signal 

Every 2 sec 

Warm up time 

2 hours (first time or using again after power off for a long time) 

2 min (operation) 

CO2 measuring range   

0~2000ppm (default) 

0~5000ppm (selected in the advanced setup) 

CO2

 

display resolution 

1ppm 

TVOC   

Sensing element 

Japan Figaro semi-conductor mixed gas sensor   

TVOC measuring range 

0-30ppm 

Temperature & Relative Humidity 

Temperature sensor (selectable) 

High precision digital integrated temperature and humidity sensor SHT,   

or NTC thermistor 

Measuring range   

-

20~60

/-4~140F (default)                  0~100%RH 

Accuracy 

Temp.: <±0.5

@25

          RH: <±3.0%RH 

20%~80%RH

 

Electrical Specification and Functions 

Power supply 

24VAC/VDC or 100-240VAC 

Power consumption 

5.5 W max. ; 2.5 W avg. 

LCD screen 

3-color TFT screen, with 4 buttons for operation   

Output   

Up to 3×  1× relay outputs or 3× relay + 1× analog outputs   

Analog: 0~10V or 4~20mA or PID 

Relay: rated current: 5A, resistance load 

CO

2

 Transmitter/Controller                 

Model

: AT-VLX series                           

 

                                 

 

User Manual 
 

Содержание AT-VLX series

Страница 1: ...ewed signal Every 2 sec Warm up time 2 hours first time or using again after power off for a long time 2 min operation CO2 measuring range 0 2000ppm default 0 5000ppm selected in the advanced setup CO2 display resolution 1ppm TVOC Sensing element Japan Figaro semi conductor mixed gas sensor TVOC measuring range 0 30ppm Temperature Relative Humidity Temperature sensor selectable High precision digi...

Страница 2: ...C Do not install the monitor on voltages higher than marked on the monitor Always turn off power before operating as follow steps Open the cover push the both clips at the bottom of the unit to remove the front cover from the back cover Please operate gently to avoid damaging of the clips Fix back cover fix the back cover on the wall according to the dimension and position see Fig 1 Connect wires ...

Страница 3: ...lease refer to Advanced Parameter P72 Table 1 DIPs setting ON OFF Default DIP1 Advances Setup Normal using OFF DIP2 AN3 output for TVOC AN3 output for RH OFF DIPs Setting End user can enter Advanced Setup by adjusting DIP1 ON and return to normal suing by adjusting DIP1 OFF DIP2 is used to adjust analog 3 when DIP2 ON analog 3 is for TVOC when DIP2 OFF analog is for RH See above Table1 Analog Outp...

Страница 4: ...ntrol mode by Advanced Setup P13 as instructed by table5 adjust humidity relay 3 control mode DIP2 OFF by Advanced Setup P14 as instructed by table 6 adjust TVOC relay 3 control mode DIP2 ON by Advanced Setup P15 as instructed by table 7 Table 4 CO2 relay 1 control mode Advanced parameter P12 value 1 2 3 4 Function Auto control ON1 decrease CO2 Auto control ON1 increase CO2 Manual control ON1 OFF ...

Страница 5: ...tion do not be recommended if not necessary Parameter Setting range Default P1 Device RS485 address 1 247 1 P2 RS485 baud rate 4800 9600 14400 19200 38400 56000 57600 115200 9600 P3 RS485 parities and stops choice 1 1stop bit None 2 2stop bit None 3 1stop bit ODD 4 1stop bit EVEN 1 P4 CO2 correction value 300 300 ppm 0 P5 Temp correction value 5 00 5 00 0 00 P6 Humidity correction value 5 00 5 00 ...

Страница 6: ...0 0 P41 Temp PID period setpoint 0 1 10000 0 0 1 P42 Temp PID P setpoint 10000 10000 2 0 P43 Temp PID I setpoint 0 0 10000 0 40 0 P44 Temp PID D setpoint 0 0 10000 0 10 0 P45 Humi PID period setpoint 0 1 10000 0 0 1 P46 Humi PID P setpoint 10000 10000 2 0 P47 Humi PID I setpoint 0 0 10000 0 40 0 P48 Humi PID D setpoint 0 0 10000 0 10 0 P49 TVOC PID period setpoint 0 1 10000 0 0 1 P50 TVOC PID P se...

Страница 7: ...isable 2 P73 relay and analog output test 0 DC1 DC2 DC3 ON1 ON2 ON3 run normally 1 DC1 0V 0mA DC2 0V 0mA DC3 0V 0mA ON1 OFF ON2 OFF ON3 OFF 2 DC1 2V 4mA DC2 2V 4mA DC3 2V 4mA ON1 OFF ON2 OFF ON3 OFF 3 DC1 10V 20mA DC2 10V 20mA DC3 10V 20mA ON1 ON ON2 ON ON3 ON 0 P74 CO2 range 0 5000ppm 2000 P75 Firmware version 862 862 Modbus Parameters Mode RTU MSB First Baud Rate 9600 14400 19200 38400 56000 576...

Страница 8: ...3 4 All button lock choice 3 6 R W 1 UINT16 1 all buttons are usable 2 ON OFF button disable 3 set buttons disable 4 all buttons disable 1 P 72 10 Co2 setpoint 3 16 R W 2 Float Big endian 0 5000ppm 800 User Co2 setpoint 12 Temp setpoint 3 16 R W 2 Float Big endian 20 0 60 0 25 User Temp setpoint 14 Humi setpoint 3 16 R W 2 Float Big endian 0 100 RH 50 User Humi setpoint 16 TVOC setpoint 3 16 R W 2...

Отзывы: