If possible, you should choose a location where 
the chimney will pass through the house without 
cutting fl oor or roof joists (see fi replace dimen-
sions 

Page 9

).

Usually, no additional fl oor support is needed 
for the fi replace.  The adequacy of the fl oor 
can be checked by fi rst estimating the weight 
of the fi replace system.  Weights are given 
on 

Page 22

.   Note the fl oor construction and 

consult your local building code to determine 
if additional support is needed. 

The Montecito fireplace may be installed 
directly on the fl oor or on a raised base (for 
proper guidelines, refer to “Hearth Extension 
Requirements”) and a minimum of 6’8” (2 m) 
measured from the base of the appliance to the 
ceiling is required.

When selecting the location, the chimney outlet 
position and the direction of the wind are impor-
tant factor affecting the chimney performance. 
To allow a maximum draft and to reduce wind 
turbulence, the chimney must:

•  Penetrate the highest part of the roof.
•  Be installed as far as possible of roof offsets, 

trees or any other obstructions that may 
cause wind turbulence and back drafts in 
the chimney.

•  The least amount of offsets (elbows) pos-

sible.

 NOTE: 

A maximum of 2 offsets is 

allowed.

GLASS CARE

Glass Replacement

The glass used for the Montecito™ fi replace is 
a high temperature ceramic glass (1,400° F / 
760° C).  If the glass breaks, it must be replaced 
with an identical ceramic glass. Tempered 
glass or ordinary glass will not withstand the 
high temperatures of the Montecito fi replace.  
Replacement glass should be purchased from a 
IHP dealer (see “Replacement Parts”, 

Page 22

)

.  

DO NOT OPERATE THE UNIT WITH CRACKED 
OR BROKEN GLASS. 

Glass Cleaning

The Montecito fi replace is designed to keep 
the glass clean under normal operating condi-
tions. If the Montecito fi replace is operated 
continuously with the combustion air controls 
closed, the glass will tend to get dirty unless 
the fuel, fi rebox and glass are maintained at 
hot temperatures (see “Refueling For Best 
Performance”).  To clean the glass, there are a 
number of specially designed cleaners.  Your 
authorized IHP dealer can recommend a suit-
able cleaner which is available in your area.  
Regular household glass cleaners will not clean 
creosote.  Do not use abrasives such as steel 
pads, steel wool or oven cleaner as they will 
scratch the glass.

DO NOT USE CHEMICAL GLASS CLEANERS 
ON PAINTED SURFACES AS IT MAY CAUSE 
THE PAINT TO PEEL.

CAUTION : DO NOT ALLOW WINDOW CLEANER 
TO GET IN CONTACT WITH DOOR GASKET OR 
PAINT ON FACADE OR DOOR.  ONCE CLOSED, 
CONTACT OF GLASS CLEANER WITH THE 
FIREPLACE FACADE CAN PROVOKE PAINT 
PEELING OFF.

Gasket

Length

Dimensions

Part No.

Steel Door

Around 
Glass

69

(1753)

1 x 3/16

(25 x 4.8)

PR-SR1685D

On Door 
Frame

73

(1854)

5/8 dia.

(15.9)

PR-SR1823G 

Cast Door

Around 
Glass

69

(1753)

1 x 5/16

(25 x 4.8)

PR-SR1823H

On Door 
Frame

73

(1854)

5/8 dia.

(15.9)

PR-SR1823G 

Table 1                      

        Inches (millimeters)

FIREPLACE INSTALLATION

Locating The Montecito Fireplace

The best location to install your fi replace is 
determined by considering the location of 
windows, doors, and the traffi c fl ow in the room 
where the fi replace is located, allowing space 
in front of the unit for the hearth extension and 
the mantel, and taking into consideration the 
location of the hot air ducts (optional), outside 
air kit and chimney.  

Gasket Replacement

Remove the door from the unit (see 

Page 7

)

 

and lay it on a clean unabrasive surface. To 
replace the gasket, fi rst remove all of the old 
gasket and gasket cement.  Make sure that the 
surface is totally clean before applying new 
cement (a high temperature silicone caulking 
rated at 500° F [260° C], is suitable) or adhesion 
problems may result.  Apply gasket cement to 
the gasket channel and install the new gasket.  
This replacement part is available from your IHP 
dealer in the following dimensions:

Marginal Location

Wind Direction

Location
Not
Recommended

Outside Air Intake
Facing the Wind

Location
Not 
Recommended

Location Recommended

Figure 30

NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

18

Содержание montecito

Страница 1: ...doors Install this fireplace in a square and plumb condition using shims as necessary at sides and or bottom Install the fireplace only as described in these instructions This installation manual will...

Страница 2: ...ensure that the air inlet to the fireplace is free from debris and any other obstructions that can block the entrance of air WARNING Neither the manufacturer nor the seller warrants smoke free operat...

Страница 3: ...ing Chimney lengths Elbows where necessary Associated components as per these installation instructions 6 diameterchimney ModelDuraTech DTC manufactured by DuraVent only including Chimney lengths Elbo...

Страница 4: ...g 10 to 20 minutes after reloading depending on the heat and on the moisture content of the wood Onceyouhavereachedthedesiredtemperature the air boost can be closed and the primary air set to a medium...

Страница 5: ...r Recommended Carbon Monoxide Poisoning Early signs of carbonmonoxidepoisoningaresimilartotheflu withheadaches dizzinessand ornausea Ifyou have these signs obtain fresh air immediately Somepeoplearemo...

Страница 6: ...NOTE The use of a firewood moisture meter is rec ommended to ensure the firewood contains less than 20 moisture Seasoning Guide Softwoods 6 months to 18 months Hardwoods 12 months to 24 months Logsth...

Страница 7: ...supplied will be necessary for this adjustment Checking Door Seal A one inch strip of paper may be used to perform a test of the integrity of the door seal Close the door on the paper in at least eigh...

Страница 8: ...ust cover the entire width of the fireplace The combustible floor in front of the fireplace must be covered with a non combustible ma terial tile marble stone etc See Figure 7 COLD CLIMATE INSTALLATIO...

Страница 9: ...instructions Product designs materials dimensions specifications colors and prices are subject to change or discontinuance without notice Allframingdimensionscalculatedfor 1 2 dry wall at the firepla...

Страница 10: ...hermal Barrier 8 Level 7 2 1 m Min 6 8 2 m Min 8 2 4 m Level 42 1067mm 2 x 3 Min 51mm x 76mm Rock Board or Other Noncombustible Facing Drywall NOTE It is recommended that the chase walls and floor be...

Страница 11: ...REPLACE BLOWER The fireplace comes equipped with a heat acti vated blower It is located in the bottom of the fireplace towards the back It uses 120V and must be connected to the main electrical circui...

Страница 12: ...a 5 diameter flexible pipe for the complete run up to thirty 30 feet and a 6 diameter pipe for a run of up to forty 40 feet The duct system must be installed respecting the following 1 Removetheplates...

Страница 13: ...Outside Intake Screw Opening Facing Down Wall Aluminum Tape Plastic Cover Insulation Flexible Pipe Aluminum Tape NOTE 2 clearancetocombustiblesaroundchimneycomponentsrequired NOTE Blown or fill type...

Страница 14: ...hing under the upper shingles and on top of the lower shingles Nail the flashing to the roof using roofing nails 6 Place the spacers and the storm collar over the flashing and tighten it with the bolt...

Страница 15: ...e a plumb bob to line up the center of the hole Cut a hole for the chimney in the ceiling floor Frame this hole as described previously refer to section Chimney Instal lation Instructions 5 From below...

Страница 16: ...6 1 8 156 mm 11 280 mm 14 1 8 359 mm 16 7 8 429 mm 18 7 16 468 mm 23 584 mm 26 3 16 665 mm B 27 11 16 703 mm 33 1 2 851 mm 50 7 8 1292 mm 62 1 2 1588 mm 72 5 8 1845 mm 78 7 16 1992 mm 95 3 4 2432 mm...

Страница 17: ...led Only one is required NOTE 45 angle for Canada only RSMI45 6DTC S45 In cold climate locations climates where temperatures will fall below 32 F 0 C we recommend that you use the insulated wall radia...

Страница 18: ...glass are maintained at hot temperatures see Refueling For Best Performance To clean the glass there are a number of specially designed cleaners Your authorized IHP dealer can recommend a suit able c...

Страница 19: ...SHT HT6103 6 dia 28 feet 8 54 m 29 feet 8 84 m DuraTech DTC 6 dia 28 feet 8 54 m 29 feet 8 84 m S 2100 HT6000 6 dia 18 feet 5 49 m 20 feet 6 1 m AC 6 dia 40 feet 12 19 m 50 feet 15 20 m Table 6 CHIMNE...

Страница 20: ...nstall the ASHT elbow on the top of the fireplace and using a level mark with an oval the location where the flue liner will enter the masonry chimney 2 In the middle of the oval drill a hole in the m...

Страница 21: ...dia 7B26ZE45 H8949 Telescopic length 8 dia 15 to 26 7B26ZLA H8950 Adjustable length 8 dia 2 5 7B26ZL2A H8951 Length two 2 feet 8KL2 H8954 Length one 1 feet 8KL1 H8953 Wall radiation shield 8 I D 7B26Z...

Страница 22: ...ron Log Retainer Bar PR SR2323 Gasket Kit Glass 69 1 x 5 16 steel and cast doors PR SR1823H Gasket Kit Steel Door Frame 73 5 8 dia PR SR1685D Gasket Kit Cast Door Frame 73 5 8 dia PR SR1823G Touch up...

Страница 23: ...Supports Offset Support SO Roof Support ST Roof Brace BS2 Firestops Firestop 6BF Radiation Shield 6RS Insulated Attic Radiation Shield 6RSA2 Insulated Wall Radiation Shield 6RSM Insulated Wall Radiat...

Страница 24: ...7B26ZR 7B26ZR Black grill with support 7B30ZO 7B30ZO Brass grill for 7B30ZK 7B30ZGB 7B30ZGB Length one 1 feet 8KL1 8KL1 Length two 2 feet 8KL2 8KL2 Length three 3 feet 8KL3 8KL3 Length four 4 feet 8KL...

Страница 25: ...may burn at excessive temperatures and may cause damage to the Product or may cause it to function improperly IHP stoves inserts and high ef ciency EPA replaces are approved for burning dry seasoned...

Страница 26: ...ntact your IHP dealer for any questions or concerns REPLACEMENT PARTS See Page 22 for a complete replacement parts list Use only parts sup plied from the manufacturer Normally all parts should be orde...

Отзывы: