Installation and Operation Instructions

Astria™ Unvented (Vent-Free) Gas Log Heater

P/N 126813-01   Rev. A   02/2014

Models

Montebello18NE

Montebello18PE

Montebello24NE

Montebello24PE

P126813-01

INSTALLER: Leave this manual with the appliance.
CONSUMER: Retain this manual for future reference.

This appliance may be installed in an aftermarket permanently located, manufactured (mobile) home, where not 

prohibited by local codes. This appliance is only for use with the type of gas indicated on the rating plate. This 

appliance is not convertible for use with other gases.

WARNING: This appliance is for installation only in a solid-fuel burning masonry or UL127 factory-built 

fireplace or in a listed ventless firebox enclosure. It is design-certified for these installations in accordance 

with ANSI Z21.11.2. Exception: DO NOT install this appliance in a factory-built fireplace that includes 

instructions stating it has not been tested or should not be used with unvented gas logs.

This is an unvented gas-fired heater. It uses air (oxygen) from the room in which it is installed. Provisions 

for adequate combustion and ventilation air must be provided. Refer to Air for Combustion and Ventilation 

section on page 6 of this manual.

 

WARNING: If the information in these instructions is not followed exactly, a fire or explosion may result 

causing property damage, personal injury or loss of life.

 

 Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other 

appliance.

 

 WHAT TO DO IF YOU SMELL GAS: 

•   Do not try to light any appliance. 

•   Do not touch any electrical switch; do not use any phone in your building. 

•   Immediately call your gas supplier from a neighbor’s phone. Follow the gas supplier’s instructions. 

•  If you cannot reach your gas supplier, call the fire department.

 

Installation and service must be performed by a qualified installer, service agency or the gas supplier.

Содержание Montebello18NE

Страница 1: ...ory built fireplace that includes instructions stating it has not been tested or should not be used with unvented gas logs This is an unvented gas fired heater It uses air oxygen from the room in whic...

Страница 2: ...rty damage Refer to this manual for correct installation and operation al procedures For assis tance or additional infor mation consult a qualified installer serviceagencyor the gas supplier WARNING T...

Страница 3: ...Keep this manual for reference It is your guide to safe and proper operation of this heater WARNING Any change to this heater or its controls can be dangerous WARNING Do not use a blower insert heat e...

Страница 4: ...owder residue within burner box or on adjacent walls or furniture 10 This heater needs fresh outside air ven tilation to run properly This heater has an oxygen depletion sensing ODS pilot light safety...

Страница 5: ...operation with flue damper closed It has been tested and approved to ANSI Z21 11 2 standard for unvented heaters State and lo cal codes in some areas prohibit the use of vent free heaters SAFETY PILO...

Страница 6: ...nconfined Space The National Fuel Gas Code ANSI Z223 1 NFPA 54 defines a confined space as a space whose volume is less than 50 cubic feet per 1 000 Btu hr 4 8 m3 per kw of the aggregate input rating...

Страница 7: ...23 1 NFPA54 theInternationalFuelGasCode or applicable local codes VENTILATION AIR Ventilation Air From Inside Building This fresh air would come from an adjoining unconfined space When ventilating to...

Страница 8: ...tural or propane LP for your unit If your gas supply is not cor rect do not install heater Call dealer where you bought heater for proper type heater NOTICE Thisheater isintended for use as supplement...

Страница 9: ...Wall Minimum 16 from Side Wall Example LOG SIZING REQUIREMENTS Minimum Firebox Size Log Size Height Depth Front Width Rear Width 18 20 14 35 22 1 2 24 20 14 35 22 1 2 Measured at 14 depth Minimum Nonc...

Страница 10: ...ove Fireplace Figure 7 Minimum Mantel Clearances When Using Hood Minimum Noncombustible Material 8 Min 12 15 18 20 2 6 8 10 12 Distances to Underside of Mantel Hood GA6050 or GA6053 Top of Fireplace O...

Страница 11: ...LOOR CLEARANCES A If installing appliance on the floor level you must maintain the minimum distance of 14 to combustibles see Figure 8 B If combustible materials are less than 14 to the fireplace you...

Страница 12: ...rchase the optional equipment shutoff valve from your dealer See Acces sories page 25 For propane LP units the installer must supply an external regulator The external regulator will reduce incoming g...

Страница 13: ...propane LP gas or opening main gas valve located on or near gas meter for natural gas or using compressed air INSTALLATION Continued Installation must include an equipment shutoff valve union and plu...

Страница 14: ...d to all joints Bubbles forming show a leak 4 Correct all leaks at once PRESSURE TESTING HEATER GAS CONNECTIONS 1 Open equipment shutoff valve see Fig ure 13 2 Open main gas valve located on or near g...

Страница 15: ...tly a fire or explosion may result causing property damage per sonal injury or loss of life A This appliance has a pilot which must be lighted by hand When lighting the pilot follow these instructions...

Страница 16: ...witch is located inside the hand held control at the top of the battery compartment Then press the receiver s reset button on the bottom of the receiver module until you hear a second longer signal Wh...

Страница 17: ...erature with set temperature and sends a signal to the receiver to turn gas valve motor up or down to adjust flame height accordingly The nighttime setback temperature TEMP appears on display The sens...

Страница 18: ...F position OPERATION Continued MANUAL LIGHTING PROCEDURE WARNING Manual lighting mustbeperformedbyaqualified service person The system has a MANUAL OVERRIDE feature that allows you to light with a mat...

Страница 19: ...bleshooting page 21 Figure 23 Correct Burner Flame Pattern Figure 24 Incorrect Burner Flame Pattern Blue Bright Yellow Flames Orange Flames INSPECTING BURNERS Check pilot flame pattern and burner flam...

Страница 20: ...g operation and have heater inspected yearly by a qualified service person We also recommend that you keep the burner tube clean and free of dust and dirt We rec ommend using compressed air no greater...

Страница 21: ...tting is not correct 9 Bad module 1 Inlet gas pressure is too low 2 Wire disconnected from gas control 3 Burner orifice s clogged 4 Bad module OBSERVED PROBLEM When and are pressed at the same time th...

Страница 22: ...f operation 1 Turn control knob to LO position and let warm up for a minute 2 Operate burner until air is removed from line Have gas line checked by local natural or propane LP gas company 3 Observemi...

Страница 23: ...tially clogged 4 Thermostat on remote is satisfied 1 Gas leak See Warning statement at top of page 2 Control valve or gas control defective 1 Foreign matter between control valve and burner 2 Gas leak...

Страница 24: ...Switch Soldered Cable Thermocurrent Cable 1 Motor Knob MAN Knob TROUBLESHOOTING Continued POSSIBLE CAUSE Battery nearly down When signal appears the first time ap proximately 10 ignitions left Cableis...

Страница 25: ...t 1 800 655 2008 When calling have ready your name your address model and serial numbers of your heater how heater was malfunctioning purchase date Usually we will ask you to return the part to the fa...

Страница 26: ...A 26 PARTS MONTEBELLO18NE MONTEBELLO18PE MONTEBELLO24NE AND MONTEBELLO24PE 1 2 3 4 5 25 22 7 8 18 9 6 10 11 26 31 34 23 12 21 20 29 28 29 28 27 24 27 24 22 13 19 14 32 30 15 15 15 15 15 15 31 15 15 15...

Страница 27: ...17004 01 117004 01 117004 01 Pilot Shield 1 20 099918 03 099918 02 099918 03 099918 02 Burner Regulator 1 21 116957 01 111803 03 116957 01 Air Shutter 1 22 111824 01 111824 01 111824 01 111824 01 Nut...

Страница 28: ...se damage to the Product will produce excessive temperatures and could result in a fire hazard c damages caused by failing to provide proper maintenance and service in accordance with the instructions...

Страница 29: ...S WARRANTY Model located on product or identification tag ______________________________ Serial No located on product or identification tag ___________________________ Date Purchased _________________...