Astria MM39VF Скачать руководство пользователя страница 7

6

Location

Note:

 You may need to provide combustion and ventilation air 

from  an  outside  source  to  adequately  satisfy  local  codes  so 

avoid installing a combustion air inlet where the opening could 

be blocked by snow, bushes or other obstacles. Note that the 

access for outside air inlet is located on the right hand side of 

the fireplace.

Internal

Wa

ll

Installation

Full

Projectio

n

Installation

Flush

Installation

Corner

Installation

Figure 3

A  flush  installation

  is  recommended  where  living  space  is 

limited or at a premium. Check local codes for any restrictions.

W

H

D

Figure 4

Model

W

H

D

MM39VF

43”

41”

28”

MM44VF

48”

41”

28”

MM49VF

53”

41”

28”

Projected installations

 can extend any distance into the room. 

A  projection  may  be  ideal  for  a  new  addition  on  an  existing, 

finished wall.

Corner installations

 make use of space that may not normally 

be used and provides a wider and more efficient range for heat 

disbursement.

An internal wall installation

  provides  a  discreet  option  for 

room  separation  and  can  also  be  ideal  as  an  addition  to  an 

existing wall.

IMPORTANT:

  Vent-free  heaters  add  moisture  to  the  air. 

Installing  a  fireplace  in  rooms  without  enough  ventilation  air 

may cause mildew to form from too much moisture.

IMPORTANT:

 Make sure the fireplace is level. If the fireplace is 

not level, the log set will not work properly.

Attention:

 You may need a building permit to install a Grand 

Meridian fireplace. Check with the local jurisdiction before you 

get started.

Supporting Floor Systems

Floor Framing

 

It is important to take into consideration that the load for the 

Grand Meridian Fireplace is considerable, but, more important, 

that it is a dead load that will have to be absorbed by a relatively 

small amount of existing floor space.

It  is  the  ultimate  responsibility  of  the  installer  to  ensure  that 

proper concrete slab supports are used.

WARNING

 to the licensed design professional and/or building 

contractor: It is your responsibility to be certain  that the Grand 

Meridian  can  be  properly  supported  by  the  combustible  floor 

system on which the fireplace will rest.

For fireplace support foundations installed on concrete refer to 

Appendix I and II (

pages 17 & 18

) for specific instructions.

Rebar locations

  Lay-out  the  position  of  the  fireplace  and  drill  holes  where 

the rebar will be located. Secure the #3 rebar 4 inches into the 

concrete foundation with ITW Epoxy or Simpson Epoxy.  Follow 

manufacturer’s instructions for installation of rebar into slab.

Wood Floor

  Anchorage of fireplace to wood floor construction is required. 

Refer to 

Figure 8

 for anchorage dimensions. Four anchors are 

required to attach to the sub-flooring framing.

Crawl Space or Upper Floor:

  For installation of firebox over combustible crawl spaces or 

upper floors, anchorage of the firebox is required. Illustrations 

of  examples  of  possible  anchorage  methods  are  shown  in 

Figures 5 thru 7 depending upon the type of floor framing. Final 

method of anchorage is to be determined by licensed design 

professional.

Содержание MM39VF

Страница 1: ...tes and approved by PFS under ANSI Z21 91 for use with any ANSI Z21 11 2 approved gas logs FOR USE ONLY WITH A LISTED GAS FIRED UNVENTED DECORATIVE ROOM HEATER NOT TO EXCEED 40 000 BTU HR DO NOT BUILD...

Страница 2: ...2007 VENTLESS FIREBOX ENCLOSURES FOR GAS FIRED UNVENTED DECORATIVE ROOM HEATERS FOR USE WITH LISTED ANSI Z21 11 2 2013 UNVENTED DECORATIVE ROOM HEATERS NOT TO EXCEED 40 000 BTU HR 0 10 NO PROJECTIONS...

Страница 3: ...d Diagram 5 9 12 2 7 1 3A 2X 2X 3X 7X 2X 8X 3 6 11 WARNING Failure to position the parts in accordance with these diagrams or failure to use only parts specifically approved with this appliance may re...

Страница 4: ...place Parts List ITEM P N DESCRIPTION QTY 1 MFP39 1 MFP44 1 MFP49 1 HEARTH Left or Right 2 2 MFP39 2 MFP44 2 MFP49 2 REAR WALL 4 3 MFP39 3 MFP44 3 MFP49 3 SIDE WALL 7 3A MFP39 3A MFP44 3A MFP49 3A SID...

Страница 5: ...rd 1 1 8 thick high temperature refractory brick is required to line the interior of the firebox These fireplaces are not intended to serve as a primary heat source rather the fireplace was expressly...

Страница 6: ...ace if not enough fresh air is available See Air for Combustion and Ventilation page 8 If the fireplace keeps shutting off see appliance manufacturers troubleshooting instructions 9 Do not run firepla...

Страница 7: ...ian fireplace Check with the local jurisdiction before you get started Supporting Floor Systems Floor Framing It is important to take into consideration that the load for the Grand Meridian Fireplace...

Страница 8: ...Meridian Fireplace must be considered as additional dead load that will have to be supported by the floor framing Additional floor joists or I joists may be required as determined by the licensed desi...

Страница 9: ...or wood structural members having a moisture content of less than 16 per cent at time of installation and used under dry conditions the deflection resulting from L 0 5D is permitted to be substituted...

Страница 10: ...designed to be custom finished with facing trim and mantle to be an owner option However all such trim material must meet standard fireplace code requirements Non combustible facing material must be...

Страница 11: ...he house to operate You must provide adequate fresh air for these appliances This will insure proper venting of vented fuel burning appliances Non combustible Flex Hose Figure 16 Exterior Providing Ad...

Страница 12: ..._ Btu hr Total _ _______ Btu hr Example Gas water heater 40 000 Btu hr Vent free fireplace 36 000 Btu hr Total 76 000 Btu hr Do not include direct vented gas appliances Direct vent draws combustion ai...

Страница 13: ...to assembly This will minimize shrinkage and cracks developing in the joint areas Best way to accomplish this is with a bucket of water and a large sponge Dip sponge into water and apply a liberal amo...

Страница 14: ...28 Apply mortar between joints 12 inch rebar 2 Mix a batch of mortar and prepare Right Side Hearth bottom surface to be bonded as shown in Figure 18 Figure 18 1 2 AWAY FROM EDGES 1 2 MORTAR BEAD TYPIC...

Страница 15: ...36 rebar to all cells as shown in Figure 22 The rebar should enter the holes in the Hearth and lie adjacent to the 12 rebar secured in subfloor Then fill cells with approx 2 cu ft Ready Mix Concrete F...

Страница 16: ...Fuel Gas Code ANSI Z223 1 This gas pipe provision must only be connected to an approved vent free gas log heater certified to ANSI Z21 11 2 heater standard Check local building codes for specific pip...

Страница 17: ...e curing We suggest operating the heater for several 30 minute intervals allowing the fireplace to cool for an hour in between This will allow any moisture in the brick and fireplace to escape Keep in...

Страница 18: ...ncrete slab The concrete strength and durability shall comply with Sections 1903 1904 and 1905 of the International Building Code IBC TABLE R402 2 MINIMUM SPECIFIED COMPRESSIVE STRENGTH OF CONCRETE MI...

Страница 19: ...ly b Lines defining areas are approximate only Local conditions may be more or less severe than indicated by region classification A severe classification is where weather conditions result in signifi...

Страница 20: ...ect for any injury or damage to the building or structure in which the fireplace has been installed or to the persons or property therein arising out of the use misuse or installation of properly manu...

Отзывы: