NOTE: DIAGRAMS & ILLUSTRATIONS ARE NOT TO SCALE.

COLD CLIMATE INSULATION

For cold climate installations, seal all cracks 

around your appliance with noncombustible 

material and wherever cold air could enter 

the room. It is especially important to insulate 

outside chase cavity between studs and under 

floor on which appliance rests, if floor is above 

ground level.  Gas line holes and other open-

ings should be caulked or stuffed with unfaced 

fiberglass insulation.  

If the fireplace is being installed on a cement 

slab in cold climates, a sheet of plywood or 

other raised platform can be placed underneath 

to prevent cold transfer to the fireplace and into 

the room.  It also helps to sheetrock inside 

surfaces and tape for maximum air tightness 

and caulk firestops.

MANUFACTURED HOUSING

B-Vent Fireplaces are not approved for use in 

OEM or aftermarket manufactured housing built 

to HUD standards.

LOCATION

In selecting the location, the aesthetic and 

functional use of the appliance are primary 

concerns. However, vent system routing to 

the exterior and access to the fuel supply are 

also important.  

Due to high temperatures, the appliance 

should be located out of traffic and away from 

furniture and draperies (Figure 3). 

En raison des températures élevées, 

l’appareil devrait être installé dans un endroit 

où il y a peu de circulation et loin du mobilier 

et des tentures (Figure 3).

The location should also be free of electrical, 

plumbing or other heating/air conditioning 

ducting.

Be aware that this is a heat producing ap-

pliance. Objects placed above the unit are 

exposed to elevated temperatures.

Do not insulate the space between the appli-

ance and the area above it.

The appliance must be mounted on a fully sup-

ported base extending the full width and depth of 

the unit. The appliance may be located on or near 

conventional construction materials. However, 

if installed on combustible materials, such as 

carpeting, vinyl tile or other combustible material 

other than wood flooring, the appliance shall be 

installed on a metal or wood panel extending the 

full width and depth of the appliance.

Figure 3  - Typical Locations

Offset Venting

** When the see-through 

fireplace is installed in the 

middle of a room, do not 

extend side walls beyond 

either viewing side of the 

fireplace.

* When the see-through 

fireplace is installed with one 

side flush with a wall, the op-

posite wall must not extend 

beyond either viewing side of 

the fireplace.

**See-Through

* See-Through 

side flush with 

a wall

Vertical Venting

Содержание Marin40STTMN

Страница 1: ...ut tre converti d autres gaz sauf si une trousse de conversion est utils e Do not store or use gasoline or other flammable vapors and liquids in the vicinity of this or any other appliance WHAT TO DO...

Страница 2: ...HER LA VITRE L cran pare tincelles fourni avec ce foyer r duit le risque de br lure en cas de contact accidentel avec la vitre chaude et doit tre install pour la protection Des enfants et Des personne...

Страница 3: ...gaalosni osalejadosde lachimeneaenfuncionamiento Superviseenformacercanaalos ni osencualquiercuartodondehaya unachimeneafuncionandopara impedirelcontactoconelvidrio Mantenga la ropa mobiliario gasolin...

Страница 4: ...appliance For use with barrier s Part No s J7420 INTRODUCTION The Millivolt appliances have a millivolt gas control valve with piezo ignition system If any optional accessories that will require elect...

Страница 5: ...h the National Fuel Gas Code ANSI Z223 1 NFPA 54 latest edition InCanada thecurrentCAN CGA B149 1 installation code The appliance when installed must be electri cally grounded and wired in accordance...

Страница 6: ...ERSION SHALL BE CAR RIED OUT BY A MANUFACTURER S AUTHO RIZED REPRESENTATIVE IN ACCORDANCE WITH THE REQUIREMENTS OF THE MANU FACTURER PROVINCIAL OR TERRITORIAL AUTHORITIES HAVING JURISDICTION AND IN AC...

Страница 7: ...ce should be located out of traffic and away from furniture and draperies Figure 3 En raison des temp ratures lev es l appareildevrait treinstall dansunendroit o il y a peu de circulation et loin du m...

Страница 8: ...1 NFPA 54 CAN CGA B149 1 Multiple Terminations These appliances may vent adjacent to and at the same level with any other gas appliances includingdirect ventappliances providedthat thereisatleast2ft 0...

Страница 9: ...tible materials may be installed at any height above the appliance opening however donotallowanythingtohangbelowthefireplacehood Minimumclearancerequirementsincludeanyprojectionssuchasshelves window s...

Страница 10: ...to appliance location Step 3 Page 13 Install the vent system and exterior termination Step 4 Page 14 Field Wiring a Millivolt Appliances The operating control switch is factory installed Step 5 Page 1...

Страница 11: ...r level a solid continuous platform must be constructed Headers may be in direct contact with the appliance top spacers but must not be supported by them or notched to fit around them All construction...

Страница 12: ...WALL BRACKET Front and back edge of unit top Stepped to accept drywall on all four corners NOTE Unit has a factory installed vent seal cap and vent cover plate see Figures 22 and 23 on page 15 in eac...

Страница 13: ...areful that the pipe compound does not get inside the pipe It is recommended to install a sediment trap in the supply line as close as possible to the appliance Appliances using Propane should have a...

Страница 14: ...olswitchwithinthemillivoltcontrolcircuit as shown in Figure 16 using the 15 feet of 2 conductor wire supplied route wires through the snap bushing to the optional control switch Mount the optional con...

Страница 15: ...er control compartment door on the side opposite the valve lifts on and off The millivolt control valve has a 3 8 10mm NPT thread inlet port Secure all joints tightly using appropriate toolsandsealing...

Страница 16: ...d crawlspace not considered part of the living area of the home NOTE Do not terminate outside air kit in attic space under any circumstances CAUTION NEVER LOCATE INLET WHERE IT CANBEBLOCKEDBYSHRUBS SN...

Страница 17: ...d clean out the ports With gas line installed run initial system checkout before closing up the front of the unit Follow the pilot lighting instructions providedintheCareandOperationInstructions manua...

Страница 18: ...lite will NOT be used See Figure 26 DO NOT PLACE ANY VERMICULITE ON THE BURNER NOTE This appliance is provided with enough Glowing Embers for several applications do not use all that is in a new bag a...

Страница 19: ...he Groove At The Bottom Of Log 1 Over The Grate And Slide It Forward Against The Grate Here Position Log 2 Over The Grate Bar And Slide It Against The Back Of The Grate Here Position Groove At The Bot...

Страница 20: ...wo Charred Spots Face The Front Position The Groove In The Back Of Log 3 Against The Grate Rest Log 5 Against The Grate Here Log 5 Sits In Front Of The Grate STEP 5 NOTICE Marin model fireplaces inclu...

Страница 21: ...the bottom of the door frame swing gently in towards the fireplace ensuring that the gasket seats evenly as the door frame draws shut Fasten the latch located underneath the firebox floor to the door...

Страница 22: ...r Clearances Figure 32 Finishing Requirements This Area Must Remain Clear of Combustible Materials Top of Appliance 1 Min 25 mm Combustible Wall Framing Spacer Clean Face Models Top of Door Frame Hood...

Страница 23: ...s safety limit switch First allow the appli ance to cool then reset the safety switch by pushing the red reset button on the back of the switch To access the blocked flue safety limit switch refer to...

Страница 24: ...usement pour liminer la poussi re et les traces de graisse ou d huile Collez l tiquette sur le bo tier de la t l commande Figure B Choisissez la langue qui est principale ment parl e dans la r sidence...

Страница 25: ...door diagonally to the left away from the fireplace Remove the modesty panel by pulling the bottom right corner of the modesty panel out slightly to disengage the snap fit feature lift the modesty pa...

Страница 26: ...ld side pressure test fitting and verify manifold pressure reads 3 5 water column 0 87 kPa for natural gas and 10 0 water column 2 49 kPa for propane gas Step 6 Refer to Figure 36 and remove the pilot...

Страница 27: ...tact avec la surface chaude Il est recommand d installer une barri re physique si des personnes risques habitent la maison Pour emp cher l acc s un foyer ou un po le installez une barri re de s curit...

Страница 28: ...ans la r sidence du propri taire En cas de doute collez l tiquette en anglais 2 Si une t l commande est utilis e pour contr ler le foyer nettoyez la soigneusement pour liminer la poussi re et les trac...

Страница 29: ...nvertible for use with other gases unless a certified kit is used These appliances are designed to operate on natural gas or propane gas only The use of other fuels or combinations of fuels will degra...

Страница 30: ...ess The glass should be kept clean during thefirsttwoweeksofusetopreventthefilmfrom baking on making it very difficult to remove See Cleaning Glass on Page 35 Orifice Sizes Sea Level to High Altitude...

Страница 31: ...On millivolt systems the piezo igniter Hi Lo flame adjustment knob and pilot and main gas ON OFF control knob are located on the modesty panel The gas valve is located behind the modesty panel See Fig...

Страница 32: ...l Knob IN OUT SIT Millivolt Gas Valve Outside Combustion Air Controls Manyappliancesareequipped wheninstalled with an outside make up air vent system that is designed to provide the appliance with out...

Страница 33: ...is safety limit switch First allow the appliance to cool then reset the safety switch by pushing the red reset button on it A To access the blocked flue safety switch 1 Remove the hood by pulling stra...

Страница 34: ...alified service technician inspectionshouldincludeensuringthatventing system is unobstructed and vent components are properly assembled and not damaged Homeowner must contact a qualified service techn...

Страница 35: ...d Generallytheglassenclosurepanels should not be removed except to gain access to the components within the firebox Removing Glass Enclosure Panels see Figure 43 To access the glass door securing latc...

Страница 36: ...be used See Figure 8 DO NOT PLACE ANY VERMICULITE ON THE BURNER NOTE This appliance is provided with enough Glowing Embers for several applications do not use all that is in a new bag at one time For...

Страница 37: ...rt Bracket Position The Groove At The Bottom Of Log 1 Over The Grate And Slide It Forward Against The Grate Here Position Log 2 Over The Grate Bar And Slide It Against The Back Of The Grate Here Posit...

Страница 38: ...55M20 4 Log Rear Right 55M21 5 Log Front Center 55M22 6 Log Center Top 55M23 2 6 5 4 1 3 Figure 47 3 Grate Assembly 5 Position Small End Of Log 6 On The Notch Of Log 3 Here 6 4 Position The Round End...

Страница 39: ...two extremes Air Shutter Adjustment Guidelines Amount of Primary Air Flame Color Air Shutter Adjustment If air shutter is closed too far Flame will be orange Air shutter gap should be increased If ai...

Страница 40: ...closed position until the proper flame appear ance is achieved 4 Leave the control knob off pilot on in the ON position millivolt appliances and the burner OFF ON switch OFF and remote switches if app...

Страница 41: ...__________________________________________ ____________________________________________________________________ Parts will be shipped at prevailing prices at time of order When ordering repair parts a...

Страница 42: ...sareavailablewithduct FOAK 4 and without duct FOAK 4LD for use if outside combustion air is required or desired If model FOAK 4LDisuseditmustbeusedinconjunction with locally purchased non combustible...

Страница 43: ...The brickaded liner kits include ceramic panels as shown here The panels have brick like features in relief ACCESSORY COMPONENTS CONTINUED H0779 Top Vent Brickaded Panel Liner Kits Model Number Catal...

Страница 44: ...terior portions of the system being exposed to cold weather Also inspect wall straps or plumbers s tape to ensure it is secure and in place Appliance Checkout Qualified Service Technician Perform the...

Страница 45: ...UCTIONS TO TURN OFF GAS TO APPLIANCE If the pilot will not stay lit after several tries turn the gas control knob to OFF and call your service technician or gas supplier 10 Turn gas control knob count...

Страница 46: ...leuse ne reste pas allum e apr s plusieurs tentatives r glez la manette d admission du gaz la position OFF et appelez un technicien qualifi ou le fournisseur de gaz 10 Tournez le bouton de r glage du...

Страница 47: ...Figures50onPage40 Cleanand oradjustpilot for maximum flame impingement on thermocouple Ensure that the connection between the valve and thermocouple are tight and secure 3 Pilot burning no gas to burn...

Страница 48: ...Black 40 J7536 2 2 Glass Enclosure Assembly 40 H6365 2 3 Log Set 55M04 1 4 Bag of Vermiculite H6319 1 5 Bag of Embers Rockwool 88L53 1 6 Bag of Decorative Volcanic Stone 80L42 1 7 Burner Assembly H62...

Страница 49: ...49 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE 2 7 10 16 22 17 18 8 23 9 20 21 5 3 19 12 4 11 Inside Location 15 NOTE See the tables on Page 48 for replacement parts applicables REPLACEMENT PARTS 13...

Страница 50: ...50 NOTE DIAGRAMS ILLUSTRATIONS ARE NOT TO SCALE NOTES...

Страница 51: ...and tear accident riot fire flood or acts of God b damages caused by abuse negligence misuse or unauthorized alteration or repair of the Product affecting its stability or performance The Product mus...

Страница 52: ...5 Innovative Hearth Products Astria MarinTN B Vent Gas Fireplace P900301 01 Innovative Hearth Products reserves the right to make changes at any time without notice in design materials specifications...

Отзывы: