PROHEAT II SERIES · HEAT PUMP AIR/WATER SYSTEM
© FLUIDRA 2019 ALL RIGHTS RESERVED. PROPRIETARY DOCUMENT.
ENGLISH
Pag: 25
temperature is lower than the "Setpoint temperature". The machine starts heating when the
probe temperature is lower than the "Temperature setpoint - Auto mode temperature
differential" and it stops heating when the temperature is higher than the "Setpoint
temperature".
6.4.2.
HEAT MODE
Start-up process:
Start-up conditions: Water intake temperature < (Setpoint temperature - Temperature
differential); and the Compressor stop time ≥ Compressor delay time
.
6.4.3.
COOL MODE (CHILLER MODELS)
Start-up process:
Start-up conditions: Water intake temperature < (Setpoint tempe Temperature
differential); and the Compressor stop time ≥
Compressor delay time