Assa Abloy Sargent 2409 Series Скачать руководство пользователя страница 5

Cover and
Screen

Chamber

Slot for screwdriver
to remove cover

RP1 Test Point

RP2 Test Point

5

Copyright © 2015, Sargent Manufacturing Company, an ASSA ABLOY Group 
company, All rights reserved. Reproduction in whole or in part without the 
express written permission of Sargent Manufacturing Company is prohibited.

A8200 (10/15)

Checking Procedures:

Turn the power to the unit “On”.  Red LED light should illuminate at 8 second 
intervals.

Open the door to the hold open point.  The door should hold open.  Manually pull 
door out of hold open and release.  The door should close.

Open the door to the hold open position.  Press the Test / Reset Switch button on 
the power supply board.  Door should close.

Press the Test / Reset Switch button again.  Open the door to the hold open position.  Inducing smoke into the 
smoke detector chamber assembly will bring the unit into alarm.  The red LED will be continuously illuminated and 
the door will close.  After clearing the smoke chamber, reset the unit as described below.

Resetting Instructions:

Remote Reset:  Cycle main power by turning the facility main power supply OFF 

then ON.   NOTE:  If there are other units connected to the same power supply, 
those doors will close.  

They will have to be reopened returning them to the hold open position.

Local Reset:  Insert a small flat head screwdriver through the cover and 

into the slotted light tube on the smoke detector as shown.  Turn screwdriver 

slightly (about 1/8 turn) clockwise until hitting stop and hold for 2 seconds 

until the Red LED turns OFF.  WARNING:  Do not force past the stop.  

Doing so may damage the smoke detector.

Once the detector is reset and the smoke has cleared, the detector’s Red LED should 

flash once every 8 seconds.  The door(s) should hold open now.

Maintenance of Smoke Detectors:
It is recommended to clean smoke detectors at least every six months.  The frequency of cleaning will depend upon 
local ambient conditions.

The smoke detector in this door closer-holder has been enhanced with a feature that detects when a smoke-sensing 
chamber requires cleaning due to dirt and dust.  The need for cleaning is indicated by the flashing of the Red LED once 
per second.

Normal Supervisory Operation - Red LED flashes once every 8 seconds.

Dirty Chamber needs cleaning - Red LED flashes once every second.

Smoke Detection - Red LED is continuously illuminated.

To clean the smoke detector assembly, follow these instructions:  
(NOTE:  Before servicing the system, notify the proper 
authorities that the smoke detector system is undergoing 
maintenance and will be temporarily out of service.  Disable the 
zone undergoing maintenance to prevent unwanted alarms.)

Remove detector cover and screen assembly using a 
standard screwdriver.  Turn the screwdriver in the cover slot 
to loosen the cover and carefully rock the cover back and 
forth until it snaps out of place.  See slot location below.

Inspect chamber for particles and dust.  Vacuum the screen, 
cover, and photo chamber.  Then use clean, compressed air 
to loosen and blow out any remaining debris.

Before reassembling the detector, be sure all parts are free of 
dust and debris.

Replace cover and screen, aligning cover snaps.  Press cover onto chamber until it snaps into place.

Measure and record the test voltage at test points RP1 and RP2 (see below).If the smoke detector is operating 
normally and was cleaned effectively, the test voltage will be greater than .90VDC and less than 1.58VDC.  
The test voltage will increase with dust accumulation in the smoke sensing chamber.  A difference in test voltages 
over time will provide and indication of dust accumulation.

Enable the system and inform proper authorities that system is operational.

Содержание Sargent 2409 Series

Страница 1: ...hru 8 of these instructions 24VDC 2409 Support Unit shown 12 2409 Master Unit shown Hinge Edge of Door Hinge Edge of Door Hinge Edge of Door INSTALLER LEAVE INSTRUCTIONS WITH BUILDING OWNER CAUTION 1...

Страница 2: ...s any of these parts could fail at any time Therefore test your smoke detector system per NFPA 72 Chapter 10 at least semiannually Clean and take care of your smoke detectors regularly Refer to Page 5...

Страница 3: ...elease their doors The unit that initiated the alarm will have its LED on The LED on the other interconnected units will flash as normal Refer to Interconnection Wiring Diagram for connections CONNECT...

Страница 4: ...h 4 pin jumper for non detectored units 120V AC INPUT CIRCUIT BOARD shown with Wiring Harness detectored units TWO PIN JUMPER WIRE SOLENOID CONNECTION WIRING HARNESS SEE PAGES 6 8 FOR ADDITIONAL WIRIN...

Страница 5: ...pen now Maintenance of Smoke Detectors It is recommended to clean smoke detectors at least every six months The frequency of cleaning will depend upon local ambient conditions The smoke detector in th...

Страница 6: ...VDC Solenoid Alarm Panel Alarm Circuit Trouble Circuit EOL Res 2 24VDC 0 15A Max To External Alarm 1 24V AC DC or 120V AC Input from Regulated Power Supply MPS10 or equiv 24V DC 0 15A Max To External...

Страница 7: ...or equiv Earth Ground 1 2 3 4 P1 P3 Circuit Board 2 1 3 Two Pin Jumper Wire 24VDC Solenoid 24V AC DC or 120V AC Input from Regulated Power Supply MPS10 or equiv Earth Ground 1 2 3 4 P1 P3 Circuit Boa...

Страница 8: ...2 3 5 4 Remote Detector Relay 4 15 10 4 4 4 15 15 15 C N O 8 Copyright 2015 Sargent Manufacturing Company an ASSA ABLOY Group company All rights reserved Reproduction in whole or in part without the e...

Отзывы: